NOTE: Switches shown in high enthalpy state. Terminals 2 and 3 close
on enthalpy decrease.

Fig. 34 — Wiring Connections for Solid-State

Enthalpy Control (HH57AC077)

CONTROL

CURVE

CONTROL POINT

(APPROX. DEG.)

AT 50% RH

A

73 (23)

B

70 (21)

C

67 (19)

D

63 (17)

RH — Relative Humidity

Fig. 35 — Psychrometric Chart for

Enthalpy Control

NOTE: Partitions shown indicate both side supply (EW/EY) and ver-
tical supply (EJ/EK) units.

Fig. 36 — Economizer Details