Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EY024-048 User Manual
Page 61

Tables 24-26 show the input and output channel
designations.
Table 24 — I/O Channel Designations Base Module — CV
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
SPT (CCN) — 10K
⍀
Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
STO (CCN) — 10K
⍀
Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5K
⍀
Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5K
⍀
Thermistor
T28-29
Heat 1 Relay — DO (24 vac)
T9-10
—
T30-29
Heat 2 Relay — DO (24 vac)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
CV Power Exhaust 1/Modulating Power Exhaust — DO (115 vac)
T13-14
—
T33-32
CV Power Exhaust 2 — DO (115 vac)
T15-16
—
T34-35
Condenser Fan — DO (115 vac)
T17-25
Y1 or Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
Y2 — DI (24 vac)
T37-38
—
T19-25
W1 — DI (24 vac)
T39-38
—
T20-25
W2 — DI (24 vac)
K1
Indoor Fan Relay — DO (LV)
T21-25
G — DI (24 vac)
K2
Compr. 1 — DO (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
Table 25 — I/O Channel Designations Base Module — VAV
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
SPT (CCN) — 10K
⍀
Thermistor
T23-25
Compressor 2 Safety — DI (24 vac)
T3-4
RAT — 5K
⍀
Thermistor
T24-25
Outside Air Enthalpy — DI (24 vac)
T5-6
OAT — 5K
⍀
Thermistor
T26-27
Economizer Pos. — AO (4-20 mA)
T7-8
SAT — 5K
⍀
Thermistor
T28-29
Heat 1 Relay − DO (24 vac)
T9-10
—
T30-29
Heat Interlock Relay — DO (24 vac)
T11-12
SAT Reset — AI (4 to 20 mA)
T31-32
Modulated Power Exhaust — DO (115 vac)
T13-14
—
T33-32
—
T15-16
—
T34-35
Condenser Fan — DO (115 vac)
T17-25
Remote Start/Stop — DI (24 vac)
T36-35
OFC2 — DO (115 vac)
T18-25
—
T37-38
Unloader 1 — DO (115 vac)
T19-25
—
T39-38
Unloader 2 — DO (115 vac)
T20-25
—
K1
Indoor Fan Relay — DO (LV)
T21-25
—
K2
Compr. 1 (HV)
T22-25
Compressor 1 Safety — DI (24 vac)
K3
Compr. 2 — DO (HV)
Table 26 — I/O Channel Designations Expansion Module (Field-Installed) — CV and VAV
TERMINAL NO.
ASSIGNMENT
TERMINAL NO.
ASSIGNMENT
T1-2
—
T23-25
Fire — Evacuation — DI (24 vac)
T3-4
—
T24-25
Fire — Smoke Purge — DI (24 vac)
T5-6
—
T26-27
—
T7-8
—
T28-29
—
T9-10
—
T30-29
Alarm Light Indicator — DO (24 vac)
T11-12
IAQ Indoor — AI (4 to 20 mA)
T31-32
Power Exhaust Fire No. 1 — DO (115 vac)
T13-14
IAQ Outdoor — AI (4 to 20 mA)
T33-32
Power Exhaust Fire No. 2 — DO (115 vac)
T15-16
—
T34-35
Power Exhaust Fire No. 3 — DO (115 vac)
T17-25
Fan Status — DI (24 vac)
T36-35
Power Exhaust Fire No. 4 — DO (115 vac)
T18-25
Filter Status − DI (24 vac)
T37-38
—
T19-25
Field Applied Status — DI (24 vac)
T39-38
—
T20-25
Demand Limit — DI (24 vac)
K1
—
T21-25
Fire — Unit Shutdown — DI (24 vac)
K2
—
T22-25
Fire — Pressurization — DI (24 vac)
K3
—
LEGEND (Tables 24-26)
AI
— Analog Input
AO
— Analog Output
CCN — Carrier Comfort Network
CV
— Constant Volume
DI
— Direct Input
DO
— Direct Output
HV
— High Voltage
IAQ
— Indoor Air Quality
K
⍀
— Kilo-Ohms
LV
— Low Voltage
OAT — Outdoor-Air Temperature
OFC — Outdoor Fan Contactor
RAT — Return-Air Temperature
SAT
— Supply-Air Temperature
SPT — Space Temperature
STO — Space Temperature Offset
T
— Terminal
VAV
— Variable Air Volume
NOTE: For 4 to 20 mA signals, all even numbered terminals are negative (−) polarity, and all odd numbered terminals are positive (+) polarity.
61