Tables 24-26 show the input and output channel

designations.

Table 24 — I/O Channel Designations Base Module — CV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

SPT (CCN) — 10K

Thermistor

T23-25

Compressor 2 Safety — DI (24 vac)

T3-4

STO (CCN) — 10K

Thermistor

T24-25

Outside Air Enthalpy — DI (24 vac)

T5-6

OAT — 5K

Thermistor

T26-27

Economizer Pos. — AO (4-20 mA)

T7-8

SAT — 5K

Thermistor

T28-29

Heat 1 Relay — DO (24 vac)

T9-10

T30-29

Heat 2 Relay — DO (24 vac)

T11-12

SAT Reset — AI (4 to 20 mA)

T31-32

CV Power Exhaust 1/Modulating Power Exhaust — DO (115 vac)

T13-14

T33-32

CV Power Exhaust 2 — DO (115 vac)

T15-16

T34-35

Condenser Fan — DO (115 vac)

T17-25

Y1 or Remote Start/Stop — DI (24 vac)

T36-35

OFC2 — DO (115 vac)

T18-25

Y2 — DI (24 vac)

T37-38

T19-25

W1 — DI (24 vac)

T39-38

T20-25

W2 — DI (24 vac)

K1

Indoor Fan Relay — DO (LV)

T21-25

G — DI (24 vac)

K2

Compr. 1 — DO (HV)

T22-25

Compressor 1 Safety — DI (24 vac)

K3

Compr. 2 — DO (HV)

Table 25 — I/O Channel Designations Base Module — VAV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

SPT (CCN) — 10K

Thermistor

T23-25

Compressor 2 Safety — DI (24 vac)

T3-4

RAT — 5K

Thermistor

T24-25

Outside Air Enthalpy — DI (24 vac)

T5-6

OAT — 5K

Thermistor

T26-27

Economizer Pos. — AO (4-20 mA)

T7-8

SAT — 5K

Thermistor

T28-29

Heat 1 Relay − DO (24 vac)

T9-10

T30-29

Heat Interlock Relay — DO (24 vac)

T11-12

SAT Reset — AI (4 to 20 mA)

T31-32

Modulated Power Exhaust — DO (115 vac)

T13-14

T33-32

T15-16

T34-35

Condenser Fan — DO (115 vac)

T17-25

Remote Start/Stop — DI (24 vac)

T36-35

OFC2 — DO (115 vac)

T18-25

T37-38

Unloader 1 — DO (115 vac)

T19-25

T39-38

Unloader 2 — DO (115 vac)

T20-25

K1

Indoor Fan Relay — DO (LV)

T21-25

K2

Compr. 1 (HV)

T22-25

Compressor 1 Safety — DI (24 vac)

K3

Compr. 2 — DO (HV)

Table 26 — I/O Channel Designations Expansion Module (Field-Installed) — CV and VAV

TERMINAL NO.

ASSIGNMENT

TERMINAL NO.

ASSIGNMENT

T1-2

T23-25

Fire — Evacuation — DI (24 vac)

T3-4

T24-25

Fire — Smoke Purge — DI (24 vac)

T5-6

T26-27

T7-8

T28-29

T9-10

T30-29

Alarm Light Indicator — DO (24 vac)

T11-12

IAQ Indoor — AI (4 to 20 mA)

T31-32

Power Exhaust Fire No. 1 — DO (115 vac)

T13-14

IAQ Outdoor — AI (4 to 20 mA)

T33-32

Power Exhaust Fire No. 2 — DO (115 vac)

T15-16

T34-35

Power Exhaust Fire No. 3 — DO (115 vac)

T17-25

Fan Status — DI (24 vac)

T36-35

Power Exhaust Fire No. 4 — DO (115 vac)

T18-25

Filter Status − DI (24 vac)

T37-38

T19-25

Field Applied Status — DI (24 vac)

T39-38

T20-25

Demand Limit — DI (24 vac)

K1

T21-25

Fire — Unit Shutdown — DI (24 vac)

K2

T22-25

Fire — Pressurization — DI (24 vac)

K3

LEGEND (Tables 24-26)

AI

Analog Input

AO

Analog Output

CCN — Carrier Comfort Network
CV

Constant Volume

DI

Direct Input

DO

Direct Output

HV

High Voltage

IAQ

Indoor Air Quality

K

Kilo-Ohms

LV

Low Voltage

OAT — Outdoor-Air Temperature
OFC — Outdoor Fan Contactor
RAT — Return-Air Temperature
SAT

Supply-Air Temperature

SPT — Space Temperature
STO — Space Temperature Offset
T

Terminal

VAV

Variable Air Volume

NOTE: For 4 to 20 mA signals, all even numbered terminals are negative (−) polarity, and all odd numbered terminals are positive (+) polarity.