Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EY024-048 User Manual

Page 40

Advertising
background image

Table 18 — User Defined Set Points

SET POINT

NAME

FORMAT

DESCRIPTION

LIMITS

DEFAULT

OHSP

xx.xF

Occupied Heat Set Point

55 to 80 F

68 F

OCSP

xx.xF

Occupied Cool Set Point

55 to 80 F

78 F

UHSP

xx.xF

Unoccupied Heat Set Point

40 to 80 F

55 F

UCSP

xx.xF

Unoccupied Cool Set Point

75 to 95 F

90 F

SASP

xx.xF

Supply Air Set Point

45 to 70 F

55 F

OATL

xx.xF

Hi OAT Lockout Temperature

55 to 75 F

65 F

NTLO

xx.xF

Unoccupied OAT Lockout Temperature

40 to 70 F

50 F

RTIO

xx.x

Reset Ratio

0 to 10

3

LIMT

xx.xF

Reset Limit

0 to 20° F

10%

MDP

xxx%

Minimum Damper Position

0 to 100%

20%

LOWMDP

xxx%

Low Temperature Minimum
Damper Position Override

0 to 100%

100%

IAQS

xxxx

IAQ Set Point

1 to 5000 PPM

650 PPM

UHDB

xx.xF

Unoccupied Heating Deadband

0 to 10° F

1° F

UCDB

xx.xF

Unoccupied Cooling Deadband

0 to 10° F

1° F

LTMP

xxx%

Low Temp. Min. Position

0 to 100%

10%

HTMP

xxx%

High Temp. Min. Position

0 to 100%

35%

PES1

xxx%

CV Power Exhaust Stage 1 Point

0 to 100%

25%

PES2

xxx%

CV Power Exhaust Stage 2 Point

0 to 100%

75%

LEGEND

CV

Constant Volume

IAQ

Indoor Air Quality

OAT — Outdoor-Air Temperature

If thermostats are used to deenergize the G input, the con-

trol board will turn off indoor fan without any delay and close
economizer dampers.

When cooling, G must be energized before cooling can

operate. The control board determines if outdoor conditions
are suitable for economizer cooling using the standard out-
door air thermistor. For economizer to function for free cool-
ing, the enthalpy must be low, the outdoor air must equal to
or less than the High Outdoor Air Temperature Lockout (de-
fault is 65 F), the SAT (supply-air temperature) thermistor is
NOT in alarm, and outdoor air reading is available. When
these conditions are satisfied, the control board will use econo-
mizer as the first stage of cooling.

When Y1 input is energized, the economizer will be modu-

lated to maintain SAT at the defined set point. The default is
55 F. When SAT is above the set point, the economizer will
be 100% open. When SAT is below the set point, the econo-
mizer will modulate between minimum and 100% open po-
sition. When Y2 is energized, the control will turn on com-
pressor no. 1 and continue to modulate economizer as described
above. If the Y2 remains energized and the SAT reading re-
mains above the set point for 15 minutes, compressor no. 2
will turn on. If Y2 is deenergized at any time, only the last
stage of compression that was energized will be turned off.
If outdoor conditions are not suitable for economizer cool-
ing, the economizer will go to minimum position and cycle
compressor no. 1 and 2 based on demand from Y1 and Y2
respectively. The compressors will be locked out when the
SAT temperature is too low (less than 40 F for compressor
no. 1 and less than 45 F for compressor no. 2.) After a com-
pressor is locked out, it can restart after normal time guard
period.

The Time Guard

௡ function maintains a minimum off time

of 5 minutes, a minimum ON time of 10 seconds, and a
minimum delay before starting the second compressor of
10 seconds.

When heating, the heat stages respond to the demand from

W1 and W2 of the thermostat input. Heating and cooling
will be mutually locked out on demand on a first call basis.
The heating and the cooling functions cannot be operating
simultaneously.

COOLING, VARIABLE VOLUME UNITS — On power up,
the control module will activate the initialization software

of the control board. The initialization software then reads
DIP switch no. 1 position to determine CV or VAV opera-
tion. Initialization clears all alarms and alerts, re-maps the
input/output database for VAV operation, sets maximum heat
stages to 1 and sets maximum cool stages to 6. The control
reads DIP switch no. 3 and if open, then it sets the internal
flag for expansion mode operation.

The control board will determine if an interface (linkage)

is active and if the unit will operate in a Digital Air Volume
(DAV) mode. In a DAV system, the room terminals are equipped
with microprocessor controls that give commands to the base
unit module. If an interface is active, the control will replace
local comfort set points, space and return air temperatures
and occupancy status with the linkage data supplied.

The control board will determine occupancy status from

Time Schedules (if programmed), Remote Occupied/
Unoccupied input, global occupancy, or DAV. If tempera-
ture compensated start is active, the unit will be controlled
as in the Occupied mode.
NOTE: The temperature compensated start is a period of time
calculated to bring the unit on while unoccupied to reach the
occupied set point when occupancy occurs.

The control board will set the appropriate operating mode

and fan control. The control board will turn VFD on if Oc-
cupied mode is evident.

For units equipped with a start/stop switch only (no space

temperature sensor), if unoccupied and valid return-air tem-
perature reading is available (either from a sensor or DAV),
the control will monitor return-air temperature against Un-
occupied Heat and Cool set points.

For units with a start-stop switch and a space temperature

sensor, the control board will start the VFD whenever SPT
is outside of the set points (Unoccupied Heat or Unoccupied
Cool). The VFD may also be started by nighttime thermostat
via remote Occupied/Unoccupied input or by a temperature
compensated start algorithm. When VFD is running in a nor-
mal mode, the control will start heating or cooling as re-
quired to maintain supply-air temperature at the supply air
set point plus the reset (when enabled). The reset value is
determined by SAT (supply-air temperature) reset and/or space
temperature reset algorithms. The space temperature reset is
only available when enabled through software.

40

Advertising