Table 9 — Power Exhaust Default Set Points

STAGE

OFFSET

DIFFERENTIAL

OFF VOLTAGE

ON VOLTAGE

OFF STATIC PRESSURE

(in. wg)

1

50%

3%

6.0

6.3

0.00

2

55%

3%

6.5

6.8

0.06

3

60%

3%

7.0

7.3

0.12

4

64%

3%

7.4

7.7

0.18

Table 10 — DIP Switch Configuration

SETTING

1

2

3

4

5

6

7

8

OPEN

VAV

VAV — Space Sensor

Installed

Expansion

Board

Field Test

ON

VAV —

Occupied

Heat

Enabled

Time Guard

Override

ON

Gas Heat

Heat Pump

Operation

CV — CCN or Sensors

Used

CV —

Modulated

Power

Exhaust

IN CONJUNCTION
WITH FIELD TEST

— Set Minimum

Damper Position

CLOSED

CV

VAV — No Space Sensor

Base Control

Board Only

Field Test

OFF

VAV —

Occupied

Heat

Disabled

Time Guard Override

OFF

Electric Heat

Air Conditioner

Operation

CV — Thermostat

CV —

Constant

Volume

Power

Exhaust

LEGEND

CCN — Carrier Comfort Network
CV

Constant Volume

VAV

Variable Air Volume

NOTES:
1. The OPEN side of the DIP switch is marked ‘‘OPEN.’’ When the

rocker switch is on the ‘‘OPEN’’ side of the switch, the switch is
OPEN.

2. The configuration of DIP switches 2 and 5 are dependent on DIP

switch 1. If DIP switch 1 is set to OPEN (VAV operation), then DIP
switches 2 and 5 will configure VAV functions.

3. When the unit is field-tested (DIP switch 4 to OPEN), the function

of DIP switch 6 changes and it is used to set the minimum damper
position.

Table 11 — DIP Switch Factory Settings

UNIT

1

2

3

4

5

6

7

8

48EJ,EW

Closed

Closed

Closed

Closed

Closed

Closed

Open

Closed

48EK,EY

Open

Closed

Closed

Closed

Closed

Closed

Open

Closed