Table 4 — Electrical Data (cont)

UNIT

SIZE

48E

NOMINAL
VOLTAGE

(3 Ph 60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER SUPPLY

No. 1

No. 2

Min

Max

RLA LRA RLA LRA Qty Hp

FLA

(ea)

Hp

FLA

FLA LRA

FLA

MCA

MOCP*

044

208/230

187

254

69.2

345

69.2

345

4

1

5.3

15

46.2/
42.0

0.96

223.1/218.9 275/275

23.6

41.6

0.96

246.7/242.5 300/300

20

59.4/
54.0

0.96

236.3/230.9 300/300

23.6

41.6

0.96

259.9/254.5 300/300

25

74.8/
68.0

0.96

251.7/244.9 300/300

23.6

41.6

0.96

275.3/268.5 300/300

460

414

508

28.8

173

28.8

173

4

1

2.7

15

21.0

0.50

96.6

125

12.6

23.6

0.50

109.2

125

20

27.0

0.50

102.6

125

12.6

23.6

0.50

115.2

125

25

34.0

0.50

109.6

125

12.6

23.6

0.50

122.2

150

575

518

632

26.7

120

26.7

120

4

1

2.4

15

17.0

0.50

86.7

110

12.6

23.6

0.50

99.3

125

20

22.0

0.50

91.7

110

12.6

23.6

0.50

104.3

125

25

27.0

0.50

96.7

110

12.6

23.6

0.50

109.3

125

048

208/230

187

254

82.1

446

69.2

345

4

1

5.3

20

59.4/
54.0

0.96

252.4/247.0 300/300

23.6

41.6

0.96

276.0/270.6 300/300

25

74.8/
68.0

0.96

267.8/261.0 300/300

23.6

41.6

0.96

291.4/284.6 300/300

30

88.0/
80.0

0.96

281.0/273.0 300/300

23.6

41.6

0.96

304.6/296.6 350/300

460

414

508

42.3

223

28.8

173

4

1

2.7

20

27.0

0.50

119.5

150

12.6

23.6

0.50

132.1

150

25

34.0

0.50

126.5

150

12.6

23.6

0.50

139.1

175

30

40.0

0.50

132.5

150

12.6

23.6

0.50

145.1

175

575

518

632

34.6

164

26.7

120

4

1

2.4

20

22.0

0.50

101.6

125

12.6

23.6

0.50

114.2

125

25

27.0

0.50

106.6

125

12.6

23.6

0.50

119.2

150

30

32.0

0.50

111.6

125

12.6

23.6

0.50

124.2

150

LEGEND

or

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Fuse or HACR circuit breaker.

NOTES:
1. In compliance with NEC requirements for multimotor and combi-

nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percent voltage imbalance.

% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v

Maximum deviation is 7 v.

Determine percent voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.