Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EY024-048 User Manual

Page 6

Advertising
background image

VFD — Variable Frequency Drive

NOTES:
1. Weights include economizer (STD).

2.

Center of gravity.

3. Do not locate adjacent units with flue discharge facing econo-

mizer inlet. Minimum clearances to be:

Adjacent Units: 15

Ј

-0

Љ

Top of Units: No overhang
Condenser Coil: 4

Ј

-0

Љ

Economizer Side: 6

Ј

-0

Љ

Gas Heat Side: 4

Ј

-0

Љ

Filter Access Side: 10

Ј

-0

Љ

(For Removal of Evaporator Coil)

4. For smaller service and operational clearances, contact

Carrier Application Engineering department.

5. Bottom ducts designed to be attached to accessory roof curb.

If unit is mounted on dunnage, it is recommended the ducts be
supported by cross braces as done on accessory roof curb.

6. Dimensions are in inches.

UNIT

SIZE

OPERATING

WEIGHT

A

B

CORNER WEIGHT (lb)

lb

ft-in.

ft-in.

1

2

3

4

48EJ,EKD038

4442

7- 8

11

16

3-10

7

8

1021 894 1180 1347

48EJE038

4602

7-10

1

8

3-11

3

16

1080 934 1200 1388

48EJ,EKD044

4668

7- 5

5

16

3-10

7

8

1033 906 1275 1455

48EJE044

4828

7- 6

13

16

3-11

3

16

1094 945 1293 1496

48EJ,EKD048

4955

7- 3

11

16

3-10

1

2

1068 953 1384 1550

48EJE048

5115

7- 5

3

16

3-10

13

16

1129 994 1401 1592

Fig. 4 — Base Unit Dimensions, 48EJ,EK038-048

6

Advertising