Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING EY024-048 User Manual
Page 7

VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.
Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet.
Minimum clearances to be:
Adjacent Units: 15
Ј
-0
Љ
Top of Units: No overhang
Condenser Coil: 4
Ј
-0
Љ
Economizer Side: 6
Ј
-0
Љ
Gas Heat Side: 4
Ј
-0
Љ
Filter Access Side: 10
Ј
-0
Љ
(For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier
Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply ductwork
connection is recommended for covering both return and both supply
openings.
UNIT
SIZE
OPERATING
WEIGHT
A
B
CORNER WEIGHT (lb)
lb
ft-in.
ft-in.
1
2
3
4
48EW,EYD024
4176
6- 0
3
⁄
8
3-6
3
⁄
8
879
954
1220
1124
48EWE024
4256
6- 1
5
⁄
16
3-6
11
⁄
16
917
973
1218
1148
48EW,EYD028
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EWE028
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
48EW,EYD030
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EWE030
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
48EW,EYD034
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EWE034
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
Fig. 5 — Base Unit Dimensions, 48EW,EY024-034
7