Table 15 — Fan Performance — Power Exhaust

48EJ,EK,EW,EY024-048 (20 THRU 45 TONS)

Airflow

(Cfm)

Low Speed

Medium Speed

High Speed

208 v

230, 460, 575 v

208 v

230, 460, 575 v

208 v

230, 460, 575 v

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

ESP

Bhp

Watts

6,500

0.32

2.82

3160

0.70

2.98

3340

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

6,700

0.23

2.87

3220

0.63

3.03

3400

0.60

3.01

3380

0.82

3.23

3620

—-

—-

—-

—-

—-

—-

6,900

0.17

2.92

3270

0.59

3.09

3460

0.55

3.07

3440

0.78

3.28

3680

—-

—-

—-

—-

—-

—-

7,100

0.13

2.93

3290

0.56

3.11

3490

0.49

3.12

3500

0.73

3.34

3740

—-

—-

—-

—-

—-

—-

7,300

0.09

2.97

3330

0.53

3.15

3530

0.43

3.18

3560

0.68

3.39

3800

—-

—-

—-

—-

—-

—-

7,500

—-

—-

—-

0.51

3.19

3580

0.39

3.24

3630

0.64

3.44

3860

—-

—-

—-

—-

—-

—-

7,700

—-

—-

—-

0.48

3.23

3620

0.33

3.27

3670

0.59

3.48

3900

0.60

3.69

4140

0.73

3.98

4460

7,900

—-

—-

—-

0.45

3.27

3670

0.27

3.32

3720

0.54

3.52

3950

0.56

3.74

4190

0.69

4.02

4510

8,100

—-

—-

—-

0.40

3.33

3730

0.22

3.36

3770

0.49

3.57

4000

0.51

3.78

4240

0.65

4.07

4560

8,500

—-

—-

—-

—-

—-

—-

0.17

3.47

3890

0.40

3.67

4120

0.41

3.83

4290

0.56

4.12

4620

8,900

—-

—-

—-

—-

—-

—-

0.00

3.58

4010

0.30

3.77

4230

0.31

3.93

4410

0.47

4.23

4740

9,300

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.22

3.87

4340

0.20

4.07

4560

0.37

4.37

4900

9,700

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.16

3.95

4430

0.11

4.17

4670

0.30

4.47

5010

10,100

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.12

4.03

4520

0.04

4.25

4770

0.23

4.56

5110

10,500

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.17

4.66

5220

10,900

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.12

4.75

5330

11,300

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.07

4.80

5380

11,700

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

—-

0.04

4.83

5420

LEGEND

Bhp

Brake Horsepower

ESP

External Static Pressure (in. wg)

Watts — Input Watts to Motor

Table 16 — Motor Limitations

STANDARD EFFICIENCY MOTORS

Nominal

Hp

Maximum

Bhp

Maximum Amps

Maximum

Watts

Motor

Efficiency

230

460

575

5

5.9

14.6

5,030

87.5

5.9

7.9

6.0

5,030

87.5

7.5

8.7

22.0

7,334

88.5

9.5

12.0

10.0

8,008

88.5

10

10.2

28.0

8,502

89.5

11.8

14.6

12.0

9,836

89.5

15

15.3

43.8

12,543

91.0

18.0

21.9

19.0

14,756

91.0

20

22.4

62.0

18,363

91.0

23.4

28.7

23.0

19,183

91.0

25

28.9

72.0

23,511

91.7

29.4

37.4

31.0

23,918

91.7

30

35.6

95.0

28,742

92.4

34.7

48.0

47.0

28,015

92.4

HIGH EFFICIENCY MOTORS

Nominal

Hp

Maximum

Bhp

Maximum Amps

Maximum

Watts

Motor

Efficiency

230

460

5

5.9

15.8

4,918

89.5

5.9

7.9

4,918

89.5

7.5

8.7

22.0

7,078

91.7

9.5

12.0

7,728

91.7

10

10.2

28.0

8,298

91.7

11.8

15.0

9,600

91.7

15

15.3

43.8

12,273

93.0

18.0

21.9

14,439

93.0

20

22.4

58.2

17,853

93.6

23.4

28.7

18,650

93.6

25

28.9

73.0

23,034

93.6

29.4

36.3

23,432

93.6

30

35.6

82.6

28,374

93.6

34.7

41.7

27,656

93.6

BHP — Brake Horsepower

NOTE: Extensive motor and electrical testing on the Carrier units has ensured that the full horsepower range of the motor can be utilized with
confidence. Using your fan motors up to the horsepower ratings shown on the Motor Limitations table will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected.