Differential Enthalpy Sensor Installation — To install the con-
trol, perform the following procedure:

1. Turn off all power. Ensure disconnect is locked out.
2. Remove the economizer inlet filters from the bottom of

the right hand economizer hood. See Fig. 24.

3. Remove the factory-installed, 620-ohm jumper between

terminals SR and + on the enthalpy control located in-
side the outdoor air hood.

4. Connect the violet wire from the enthalpy sensor kit to

the + terminal on the enthalpy control. Connect the blue
wire from the enthalpy sensor kit to the SR terminal on
the enthalpy control.

5. Turn the enthalpy control set point potentiometer clock-

wise past the ‘‘D’’ setting on the enthalpy control to con-
figure the control to operate on differential enthalpy. See
Fig. 34.

6. Remove the return-air enthalpy sensor from the acces-

sory package. Using the screws provided, mount the sen-
sor inside the return duct near the unit. Do not locate the
control too far from the unit, or the wires will not reach
from the sensor to the control. On 48EW/EY units, the
enthalpy sensor can be installed in the return air section
of the unit, under the return air dampers.

7. Route the wires from the enthalpy sensor to the return

air enthalpy control through the holes on the inside of
the hinged filter access panel. The holes are blocked by
plug buttons which should be removed.

8. Use field-supplied wire ties to attach the violet wire to

the + terminal and the blue wire to the SR terminal.

9. Replace economizer filters.

10. Return power to unit.

Disable Economizer — For applications where the econo-
mizer will not be used (areas of high humidity), the econo-
mizer should be disabled. To disable the economizer, perform
the following:
1. Turn of power. Lock out disconnect.
2. Locate the OAT (Outdoor Air Thermostat) in the right

hand outdoor air damper area.

3. Locate the splice connecting the violet wire coming from

T24 on the base module board to the red wire coming
from T29 on the base module board. Remove the wire
nut and break the red to violet wire splice.

4. Cap off both wires. When the connection is broken the

base module is fooled into thinking that the enthalpy is
not acceptable and economizer operation is disabled.

MOUNTING ANGLE
(WITH TABS)

Fig. 31 — Mounting Angle (With Tabs) Attached to

Filter Track Assembly

BLACK SEAL STRIP
(CENTERED)

FILTER COVER

Fig. 32 — Attaching Seal Strip to Filter Cover

HH57AC077

ENTHALPY CONTROL

+

C7400A1004

Fig. 33 — Differential Enthalpy Control and Sensor

HH57AC078

ENTHALPY SENSOR

(USED WITH ENTHALPY

CONTROL FOR DIFFERENTIAL

ENTHALPY OPERATION)