VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.
Center of gravity.
3. Do not locate adjacent units with flue dis-
charge facing economizer inlet. Minimum clear-
ances to be:
Adjacent Units: 15
Ј
-0
Љ
Top of Units: No overhang
Condenser Coil: 4
Ј
-0
Љ
Economizer Side: 6
Ј
-0
Љ
Gas Heat Side: 4
Ј
-0
Љ
Filter Access Side: 10
Ј
-0
Љ
(For Removal of
Evaporator Coil)
4. For smaller service and operational clear-
ances, contact Carrier Application Engineer-
ing department.
5. Bottom ducts designed to be attached to ac-
cessory roof curb. If unit is mounted on dun-
nage, it is recommended the ducts be
supported by cross braces as done on ac-
cessory roof curb.
6. Dimensions are in inches.
UNIT
SIZE
OPERATING
WEIGHT
A
B
CORNER WEIGHT (lb)
lb
ft-in.
ft-in.
1
2
3
4
48EJ,EKD024
4176
6- 0
3
⁄
8
3-6
3
⁄
8
879
954
1220
1124
48EJE024
4256
6- 1
5
⁄
16
3-6
11
⁄
16
917
973
1218
1148
48EJ,EKD028
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EJE028
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
48EJ,EKD030
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EJE030
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
48EJ,EKD034
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
48EJE034
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
Fig. 3 — Base Unit Dimensions, 48EJ,EK024-034