LAARS Heating Systems

Page 112

Code Description

L or

H

Procedure

237

Invalid DHW (Domestic Hot Water)

connector type setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

238

Invalid Stack connector type setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

239

Invalid Header connector type setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

240

Invalid Outdoor connector type setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.