LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 119

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 115

12.8 Control Snapshot

The software allows you to take a “snapshot” of

the current state of the controller, including setup

information and operating information. This

information can be helpful during troubleshooting.

How to get there –
Home Page <Setup button> Setup Screen <Control

Snapshot button> Control Snapshot Screen

Figure 138 shows the Control Snapshot screen.

Fig. 138 - Control Snapshot List Screen

Select one of the controllers listed on the right side

of the screen. Press one of the buttons below the

right column to see the snapshot. See Fig. 139.

Fig. 139 - Typical Control Snapshot

The Show Status button captures the current status

of the I/O of the control only. Show Configuration

captures the current parameter settings and the

control setup. You can save the snapshot, give it a

name, or send a copy to the USB port.

12.9 Operating Sequence

Initiation
Each controller enters the Initiation sequence after

one of these conditions:

Initial power up

Voltage fluctuations vary +10% or -15%

Frequency fluctuations vary ±10%

The demand, limit control input, or TT signals

are interrupted during the prepurge period.

After the Reset button is pressed.

After a Fault is cleared using the displays.

The Initiation sequence also delays the boiler

demand from being energized and re-energized from

an intermittent AC line input or control input. If

an AC problem exists for more than 240 seconds, a

lockout will occur.

Start-Up Checks in a Lead/Lag System
For an explanation of Lead/Lag operation, see the

first part of Section 9. In this section, we will focus

on the aspects of Lead/Lag that might be helpful in

troubleshooting.
When a Lead/Lag system is first powered up, the

controller acting as the Lead/Lag Master goes

through a “synchronization” process. During

synchronization, the controller establishes

communications with each of the Slave controllers

via the Modbus link. The Slave controllers

download some setup parameters and operating

history information. (On a system with several

boilers, this phase can take several minutes.) If the

Master cannot establish communications with one of

the Slaves, it triggers a Hold or Lockout.
The Master also checks the status of each of the flap

valves. If the Master cannot determine whether a

flap valve is open or closed, or if it cannot locate the

correct number of flap valves, it triggers a lockout or

hold.
If the system passes the checks described above,

each of the individual controller and burner

combinations is free to operate in the normal

way. The self-check and firing sequence for each

individual controller and burner combination is

described in the following section.

Advertising