LAARS Heating Systems

Page 80

9.6

Gateway Connections to a

Building Automation System

NeoTherm LC boilers can be controlled and

monitored through the included Modbus ports. The

Modbus wiring should be completed according

to the instructions in this manual. If alternate

communication protocols are desired, Laars offers

“gateways” to allow BACnet, LON, and other

communications protocols. Signals from a Building

Automation System can be connected to TB10. See

Fig. 120. For additional information on setting up

Modbus and other communication protocols, contact

the factory.

Fig. 120 - BAS Connections

Fig. 121 - Enabling COM2

Enabling Modbus Port 2 -
For this system to work correctly, Modbus Port 2 on

the unit operating as the Lead/Lag Master must be

enabled. From the ‘home’ screen, press the Setup

button to go to the Setup screen. Press the Display

Setup button to go to the Display Setup screen. On

the Display Setup screen, press the COM2 tab to

bring up the setup screen for the COM2 function.

Click the box labeled “Enable COM2 Port.” See

Fig. 121.

9.7

Setup for High Altitude

Operation - NT 1700 Only

(This is an individual function – do this for each of the controls
Use the separate Touch Screen on each boiler.)

When setting up a NT 1700 unit in a high altitude

environment, a low fire adjustment must be made.

The Minimum Modulation rate (RPM) must be

increased from 2100 RPM to 2500 RPM. You will

need to do this in the primary control, then again in

the secondary control on each boiler.

How to get there – Minimum Modulation Rate
Home Page < Select one of the controller icons > NeoTherm
LC Primary (or Secondary) screen < Press Configure button
> Configuration Menu screen < Press line for Modulation
Configuration > Modulation Configuration screen < Go to line
for Minimum Modulation Rate, press box > < System asks you
to login, press Lock symbol at top of screen > Keyboard screen
< Type in installer-level password, then Enter > < Return to line
for Minimum Modulation Rate, press Clear, type “2500”, then
Enter >

Remember to do this for both the primary and

secondary controls on each of the boilers.