NeoTherm LC Boilers and Water Heaters

Page 65

DHW time of day setpoint -

Separate Time-of-Day Setpoint for Domestic

Hot Water (See the material on “About the

‘Time of Day’ Function at the end of this

section)

Modbus port -
Always use MB1

4. To see the other settings related to the Lead/

Lag functions, press the button for Advanced

Settings. This leads to a “ring” of related

screens, and you can scroll through the list

by pressing one of the left- or right-arrow

symbols. The screens in this ring are:

Modulation
Central Heat
Domestic Hot Water
Frost Proection
Outdoor Reset
Warm Weather Shutdown
Algorithms
Rate Allocation
Add Stage
Drop Stage

5. Press the left-arrow or right-arrow until you

see the Modulation screen (Fig. 83).

Fig. 83 – Modulation

Three of the items on this screen can be

changed:

Off hysteresis -

The system will not shut off the burners

until the System sensor reaches the CH

Setpoint plus an additional “hysteresis”

value.

On hysteresis -

The system will not fire the burners until

the System sensor reaches the LL CH

Setpoint minus an additional “hysteresis”

value.

P, I, D Gain -

These control the “damping” used by the

temperature control. The three control

values are P (proportional), I (integral)

and D (derivative). If you understand how

these variables affect the function of the

unit, you can change them to adjust for

unusual operating conditions. The default

settings for the Lead/Lag configuration are:

P = 30, I = 20, and D = 0.

6. Press the left-arrow or right-arrow until you

see the Central Heat screen (Fig. 84).

Fig. 84 – Central Heat

Setpoint source -

This sets the source of the System sensor

input used to control the system. The

options here are Local and 4-20 mA.

(For instructions on setting up for a 4-20

mA input, see Job #5 in the section on

“Installation Options.”)

Setpoint -

This is the same as the LL CH Setpoint on

the Lead/Lag Master Configuration screen

(Fig. 82).

Time of day setpoint -

This is the same as the LL CH Time-Of-

Day Setpoint on the Lead/Lag Master

Configuration screen (Fig. 82). (See the

material on “About the ‘Time of Day’

Function at the end of this section)

4 mA water temperature -

If a 4 – 20 mA input is used to adjust the

setpoint, this entry sets the low limit of the

control range. (In the example shown here,

an input of 4 mA would result in a setpoint

of 90°F.)