LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 70

Advertising
background image

LAARS Heating Systems

Page 66

20 mA water temperature -

If a 4 – 20 mA input is used to adjust the

setpoint, this entry sets the high limit of the

control range. (In the example shown here,

an input of 20 mA would result in a setpoint

of 120°F.)

7. Press the left-arrow or right-arrow until you

see the Domestic Hot Water screen (Fig. 85).

Fig. 85 – Domestic Hot Water

The arrangement for Domestic Hot Water can

be set up in several ways. For details, see the

section on “Lead/Lag Domestic Hot Water.”

DHW Setpoint -

This is the same as the DHW Setpoint on

the Lead/Lag Master Configuration screen.

DHW Time of day setpoint -

This is the same as the DHW Time-Of-

Day Setpoint on the Lead/Lag Master

Configuration screen. (See the material on

“About the ‘Time of Day’ Function at the

end of this section.)

DHW Priority method -

This determines the way the system gives

priority to the DHW demand (if DHW is

given priority on the bottom line of the

screen.)

DHW priority override time -

If Domestic Hot Water has priority (see

the next line below), this sets how long

the DHW loop will have priority before

returning to control by the Lead/Lag Central

Heat setpoint.

DHW has priority over CH? -

Choose Central Heating priority or

Domestic Hot Water priority.

8. Press the left-arrow or right-arrow until you

see the Outdoor Reset screen (Fig. 86).

Fig. 86 – Outdoor Reset

“Outdoor Reset” allows the system to adjust

the Central Heat setpoint to compensate

for changes in the outdoor temperature.

This allows the whole system to run more

efficiently. For details, see the section on

“About Outdoor Reset.”

Enable -

Enable = Outdoor Reset feature turned on

Max. outdoor temp. -

If the outdoor temperature reaches this value

or above, the system will use the Low Water

Temp value as the setpoint. In the example

shown in Fig. 86, the Max. Outdoor Temp.

is set to 70°F. If the outdoor temperature is

70°F or above, the system will use 100°F

(the Low Water Temp.) as the setpoint.

Min. outdoor temp. -

If the outdoor temperature reaches this value

or below, the system will not compensate

for the outdoor temperature. In the example

shown in Fig. 86, the Min. Outdoor Temp.

is set to 32°F. If the outdoor temperature

reaches 32°F or below, the system will

use the normal Lead/Lag System setpoint

(120°F in this example).

Advertising