LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 62

Advertising
background image

LAARS Heating Systems

Page 58

Job E – Set Up the Modbus Control

Addressing

(This is an individual function – do this for each of the controls
Use the separate Touch Screen on each boiler.)

Do this on any system with multiple boilers.

Note – Do not connect the Modbus wiring yet. The

controls must be set up and addressed correctly

before the wiring is complete. If the wiring is

attached before the control Modbus addresses are

changed, there will be multiple controls with the

same address, and the system will not work.

1. When the system is operating under the

control of the Lead/Lag system, the Lead/Lag

Master needs a way to identify each controller

in each of the boilers. On a system with four

boilers there will be eight separate controllers.

You will need to give each of these controllers

a unique Modbus address. (Notice that this is

different from the name of the controller. We

set the controller names in a previous step.)

2. Power up all of the boilers in the system. It

will take a minute for each Touch Screen to

“synchronize” with its two controllers.

3. Start at the ‘home’ screen on the first boiler.

See Fig. 63.

Fig. 63 – ‘home’ screen

4. Press the Setup button in the lower right-hand

corner to go to the Setup screen.

Fig. 64 – Setup Screen

5. Press the Control Setup button. Figure 65

shows the Control Setup screen.

Fig. 65 – Control Setup Screen

6. The first number on each line (01, 02, etc.) is

the Modbus control address. Let’s set up the

Modbus address for the first controller in the

line - the Primary controller on Boiler 1. Press

the top line – NeoTherm LC Primary.

7. Press the Change Address button. You need to

know the installer-level password to change

the address, so the system will ask you to log

in. (For more information on the passwords

and logging in, see the section on “Using the

Touchscreen.”) Press the padlock symbol in

the upper right-hand corner of the screen, then

type in the installer-level password and press

the OK button.

8. Press the Change Address button again. The

system will present a screen that lets you

change the address.

Fig. 66 – Changing Modbus Address

9. Table 13 shows how the Modbus control

addressing should be set up. The system is

simple, but it is important to only use the

correct address listed in the table. Do not

use any other address than the one listed in

the table for the control you are addressing.

In this example, the correct address for the

Advertising