LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 25

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 21

6A.3 NTH Freeze Protection

WARNING

Glycol must not be used in domestic hot water

applications. Refer to Section 6B.4 for instructions

on freeze protection for NTV units (domestic hot

water).

NeoTherm LC’s may be installed indoors or

outdoors. If installed outdoors, the NTH unit

must never be installed in a location which may

experience freezing temperatures. If installed

indoors, and there is an event such as a power

outage, interruption of gas supply, failure of system

components, activation of safety devices, etc., this

may prevent a boiler from firing. Any time a boiler

is subjected to freezing conditions, and the boiler

is not able to fire, and/or the water is not able to

circulate, there is a risk of freezing in the boiler

or in the pipes in the system. When water freezes,

it expands. This may result in bursting of pipes, or

damage to the boiler, and this could result in leaking

or flooding conditions.
Do not use automotive antifreeze. To help prevent

freezing, Laars recommends the use of inhibited

glycol concentrations between 20% and 35% glycol.

Typically, this concentration will serve as burst

protection for temperatures down to approximately

-5°F (-20°C). If temperatures are expected to be

lower than -5°F (-20°C), glycol concentrations up

to 50% can be used. When concentrations greater

than 35% are used, water flow rates must be

increased to maintain a 20°F to 25°F temperature

rise through the boiler.
Different glycol products may provide varying

degrees of protection. Glycol products must

be maintained properly in a heating system, or

they may become ineffective. Consult the glycol

specifications, or the glycol manufacturer, for

information about specific products, maintenance

of solutions, and set up according to your particular

conditions.
The following manufacturers offer glycols,

inhibitors, and anti foamants that are suitable

for use in the NeoTherm LC. Please refer to the

manufacturers instructions for proper selection and

application.
• Sentinel Performance Solutions Group
• Hercules Chemical Company
• Dow Chemical Company

6A.4 NTH Suggested Piping Schematics

Figures 12 through 16 (the next several pages) show

suggested piping configurations for NTH boilers.

These diagrams are only meant as guides. All

components or piping required by local code must

be installed.

6A.5 Condensate Drain Trap

A condensate drain trap is included with the

NeoTherm LC and is designed to drain the boiler

of condensate. The vent condensate should be

drained through a drain tee located in the vent line.

This will help prevent excessive condensate from

entering the boiler condensate trap and preventing

the boiler from operating.
Connect a 3/4” PVC pipe between the drain

connection and a floor drain (or condensate pump if

a floor drain is not accessible).
The condensate drain must be installed to prevent

the accumulation of condensate. When a condensate

pump is not used, the tubing must continuously

slope downward toward the drain with no spiraling.
Consult local codes for the disposal method.

Caution

Condensate is mildly acidic (pH=5), and may

harm some floor drains and/or pipes, particularly

those that are metal. Ensure that the drain,

drainpipe, and anything that will come in

contact with the condensate can withstand the

acidity, or neutralize the condensate before

disposal.

Damage caused by failure to

install a neutralizer kit or to adequately treat

condensate will not be the manufacturer’s

responsibility.

Advertising