LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 71

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 67

Low water temp. -

If the outdoor temperature reaches the Max.

Outdoor Temp. or higher, the system will

use the Low Water Temp value as the new

setpoint. In the example shown in Fig. 86,

the Max. Outdoor Temp. is set to 70°F. If

the outdoor temperature reaches 70°F or

above, the system will use the Low Water

Temp. value (100°F) as the setpoint.

Min. boiler water temperature -

If a value is entered here, the temperature

in the boiler will never be allowed to drop

below this temperature. This will protect

the boiler against possible damage due to

expansion of ice inside the unit.

9. The Show Line button at the bottom of the

screen displays a curve which shows how

the system will behave at different outdoor

temperatures. See Fig. 87. (This screen

is also explained in the section on “About

Outdoor Reset.”)

Fig. 87 – Outdoor Reset Display

10. From the Outdoor Reset screen, press the left-

arrow or right-arrow until you see the Warm

Weather Shutdown screen (Fig. 88).

Fig. 88 – Warm Weather Shutdown

When enabled, the Warm Weather Shutdown

feature will turn off the Central Heating

functions when the outdoor temperature

exceeds the setpoint. This prevents the system

from running when there is no need for heat.

Enable -

These options determine how quickly

the system shuts down after the outdoor

temperature rises above the setpoint. The

options are Shutdown immediately/ After

demand ends/ Disabled.

Setpoint -

If the outdoor temperature is higher than

this, the system will shut off the Lead/Lag

Central Heating functions.

11. Press the left-arrow or right-arrow until you

see the Rate Allocation screen (Fig. 89).

Fig. 89 – Rate Allocation

As the load on the system increases, the first

boiler in the Lead/Lag chain will increase the

fan speed until it reaches a certain percentage

of the total output (the “base load”). At that

point, the controller will start the second boiler

in the lead/lag chain. See the explanation at

the beginning of this section and Fig. 50.

Base Load Common -

As the demand increases, this sets the point

at which the controller starts another burner

in the Lead/Lag chain.

To prevent short-cycling, the base load setting

should be set at the values shown in Table 16,

or set to higher values.

Advertising