LAARS Heating Systems

Page 74

9. You can change the fan speed of the burner

by adjusting the value entered for Firing Rate

on the right side of the display. (Remember, a

moment ago you selected the Primary control

for this boiler, so this change will only affect

the Primary burner.) Press the yellow box

beside the Firing Rate label.

10. The system will ask you to log in using a

password. Enter the installer-level password,

then press OK.

11. Press the box for Firing Rate again. The

controller will present the Manual Firing Rate

screen shown in Fig. 104.

Fig. 104 - Manual Firing Rate

12. Notice the three options on the left side of the

screen:

Auto -

The firing rate will be set automatically by

the controller, based on the heat load. Set this

item to Auto at the end of the test.

Manual in Run -

The Manual in Run control will only set the

fan speed when the control has proven flame

and the unit has entered the Run mode.

Manual in Run and Standby -

Using this setting, the manual control will set

the fan speed whether the boiler is operating

or not.

For this test, select Manual in Run.

13. Type in a value for high fire RPM. Enter 8000

RPM. (The actual RPM will not go this high

– the control will limit the fan speed to the

maximum set at the factory.)

By using the manual control, and entering a

high RPM value, this forces the burner to run

at full combustion so you can adjust the gas

valve for the correct CO

2

output.

Figures 105 and 106 show the adjusting points

on the gas valve. Adjust the High Fire screw

to get the proper CO

2

level for high fire. See

Table 17. To raise the high fire CO

2

level,

Fig. 105 – Connections for

Pressure Gauge - NT 1000

Positive connection point

Negative connection point

Fig. 106 – Connections for

Pressure Gauge - NT 1700

Negative
connection
point

Positive
connection
point