LAARS Heating Systems

Page 42

Fig. 43 - Verification Needed

Notes –

• Once you change one of these safety-related

parameters, you

must finish the verification

process for the group that includes the parameter,

or the control system will not let the boiler

operate. You can wait to do the verification until

you have changed parameters in other groups,

but before you return the boiler to service, you

have to do the verification for all of the groups you

changed.

• At the end of the verification process, you

must press the Reset button on the front of the

controller. See Fig. 44. You have to do this within

30 seconds, or the verification will be cancelled.

To make it easy to reach the Reset button, open

the door on the front of the boiler and slide out the

control panel

before beginning the verification.

Fig. 44 - Reset Button on Controller

3. Don’t press the Reset button yet. We just want

to show you where the Reset button is located.

Change the parameter(s) you want to change.

4. When you are done entering parameters, the

next job is to do the verification. Login to the

system and press Begin.

Fig. 45 - Edit Safety Data

5. Once you are done changing safety

parameters, press Confirm. The system will

present a listing for each group of parameters

which includes a changed safety parameter.

See Fig. 46.

Fig. 46 - Safety Parameter Confirmation

6. For each group, check the list carefully. Press

Yes if all of the parameters in the group have

been entered correctly.

If you made changes in other safety-related

groups, verify the entries in those groups in

the same way. When the process is complete,

the system will tell you to reset the control

system.