LAARS NeoTherm LC NTV1700 - Install and Operating Manual User Manual

Page 83

Advertising
background image

NeoTherm LC Boilers and Water Heaters

Page 79

4. Select that line by pressing it. If you want

to change the DHW priority, the system will

ask you to log in using the installer-level

password. For this kind of installation, the

entry should be “DHW> CH.”

5. Go to the line for “DHW Priority vs Lead

Lag.” For this kind of installation, the entry

should be “DHW> LL.”

6. Remember to change the settings on the other

controller/burner for this boiler.

Setup Type 3 –
The third possibility is to set up a single boiler that just

provides domestic hot water. The model NTV unit is

designed for this kind of “volume water” service. The

water is heated as it moves through the boiler, and that

same water is supplied directly for domestic use. This

is really like a conventional Lead/Lag setup, except

priority is given to domestic hot water, and there is no

input for the central heating function.

• On each boiler which will operate this way,

connect a DHW sensor or the input from the

aquastat to terminals 5 and 6 on TB6. Be

sure there is no thermostat connected (check

terminals 5 and 6 on TB7).

• The two burners in each boiler will operate

in the Lead/Lag mode. You can think of each

boiler as a separate two-burner Lead/Lag

system.

• The setpoint used is the LL DHW setpoint, set

as part of the Lead/Lag system.

• In the Lead/Lag setup, DHW is given priority.

1. Start at the ‘home’ screen (Fig. 116).

Fig. 116 – ‘home’ screen

2. Press the Lead Lag Master button. Fig. 117

shows the screen that follows.

Fig. 117 – Lead/Lag Master Screen


3. Press the Configure button. The display will

present the Lead/Lag Master Configuration

Screen (Fig. 118). Set the DHW setpoint on

this screen.

Fig. 118 – Lead/Lag Master Configuration

4. Press the button for Advanced Settings. This

leads to a “ring” of related screens, and you

can scroll through the list by pressing one of

the left- or right-arrow symbols. Press the

left-arrow or right-arrow until you see the

Domestic Hot Water screen (Fig. 119).

Fig. 119 – Domestic Hot Water

Set the last line to give priority to the DHW

function.

Advertising