Table 14 – Number of Controls

Number of

boilers

Number of

controls

2

4

3

6

4

8


For example, if your system has three boilers,

there would be a total of six controllers (two

for each boiler), so you would enter “6” for

Number of Controls.

5. Press the line for Controller ID. Because you

are changing a parameter that is related to

safety, the system will present a warning that

looks like this:

Fig. 72 – Parameter Safety Warning

Press OK to continue. The system will ask

you to login before you make a change.

Note that any changes you make will apply

only to one controller – the controller you

have already selected. If you want the same

change to apply to other controllers, you must

change each of them separately.

Once you change one of these safety-related

parameters, you must finish the verification

process, or the control system will not let the

boiler operate. Each control in a boiler must

be verified separately.

6. Press again on the line for Controller

ID. Table 15 shows how the Primary and

Secondary controls should be numbered for

each of the boilers.

In this example, we are still working with the

Primary control for Boiler 1. From the table,

you can see that this control should have a flap

valve ID of “1.” Enter the correct ID from

Table 5 in this field.

WARNING

If the controller cannot find a signal from one

of the flap valves, the control system will act to

prevent backflow by energizing the blower of the

control with the bad flap valve. If this cannot be

done the control will not allow the whole system to

run. For this reason, it is important that all of the

flap valves be identified correctly.

7. Set the address for the other controller on this

boiler in the same way.

8. At this point, you have set the flap valve ID’s

for both controllers on this boiler. Before you

leave, you must finish the verification process,

or the control system will not let the boiler

operate.

Press the Back arrow to return to the

Configuration screen.

Fig. 73 – Configuration Screen

9. In a moment, you will need to reset the

controller by pressing a button on the front of

the unit. See Fig. 74. The controllers for the

two boilers are mounted behind the door on

the front of the unit.

Boiler 1

Boiler 2

Boiler 3

Boiler 4

Primary control

1

3

5

7

Secondary control

2

4

6

8

Table 15 – Flap Valve Controller ID Addressing