Power requirements for the cisco telepresence 3200 – Cisco 3200 User Manual

Page 156

Advertising
background image

9-2

Cisco TelePresence System 3200

OL-14521-01

Chapter 9 Routing Power and Signal Cables

Power Requirements for the Cisco TelePresence 3200

Caution

Do not power on the PDUs until you route and connect all the cables.

Caution

Use care when you route the power cables from the PDUs. Do not bend the cables immediately after they
exit the PDUs and be sure that the cable does not pull on, or cause any strain to, the PDU socket and
power cord plug connection. Incorrectly routed cables can cause undue stress to the PDU receptacle and
the power cord plug.

Warning

Overcurrent protection is provided by branch circuit protection rated 20A.

Warning

Output receptacles cannot exceed 15A for any one receptacle.

Power Requirements for the Cisco TelePresence 3200

Table 9-1

provides the power requirements and PDU locations for the Cisco TelePresence 3200 system.

Caution

Correct routing of the various power cords to the PDUs and auxiliary control unit is critical for the safety
and success of the Cisco TelePresence 3200. Route each power unit to a different 20 amp circuit to
prevent circuit overload when all the electrical components are properly installed.

Table 9-1

PDU and Auxiliary Control Unit Locations and Power Requirements

Left PDU 1

(Located on Left Accessory Cabinet)

AC wall outlet

20 amps @100-120volts

or 10 amps @ 230-240 volts

Right PDU

(Located on Right Accessory Cabinet)

AC wall outlet

20 amps @100-120volts

or 10 amps @ 230-240 volts

Auxiliary Control Unit

(Located on rear of display structure)

AC wall outlet

20 amps @100-120volts

or 10 amps @ 230-240 volts

First Row Table PDU

(Located above the projector under the Center table segment)

AC wall outlet

20 amps @100-120volts

or 10 amps @ 230-240 volts

Second Row Table left-center PDU

20A AC wall outlet

Second Row Table right-center PDU

20A AC wall outlet