Vent and combustion air piping, Single pipe (n9mp1 models), Direct vent (n9mp2 models) – Sears 9MPD User Manual

Page 11: Dual certified f 9mpd models), Contaminated combustion air, Vent and combustion air piping guidelines, Vent & combustion air piping

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

4. Vent and Combustion Air Piping

CARBON MONOXIDE POISONING, FIRE AND EXPLO­
SION HAZARD

Failure to properly vent this furnace can result in death,

personal injury and/or property damage.

Read and follow all instructions in this section.

Single Pipe (N9MP1 Models)

This furnace is certified as a category IV appliance. This furnace
requires ventilation openings to provide air for proper combustion
and ventilation of flue gases. All duct or openings for supplying
combustion and ventilation air must comply with the gas codes or
in absence of local codes, the applicable national codes.

When the installation is complete, see the "

Venting and Com­

bustion Air Check'

in this manual.

Direct Vent (N9MP2 Models)

This furnace is certified as a category IV appliance. This furnace
uses outside air for combustion ONLY, it MUST be taken from the
same atmospheric pressure zone as the vent pipe. See

Con­

fined Space Instailation

in the

Combustion and Ventilation

Air

in this manual.

Dual Certified f 9MPD Models)

This furnace is certified as a category IV appliance. This furnace
can be installed as a direct vent furnace using outside air for com­
bustion or the furnace can use air from inside the structure for
combustion. The INLET air pipe is optional. If combustion air
comes from inside the structure, adequate make up air MUST be
provided to compensate for oxygen burned. See

Confined

Space Installation

in the

Combustion and Ventilation Air

chapter. If combustion air is drawn from outside the structure, it
MUST be taken from the same atmospheric pressure zone as the
vent pipe.

Contaminated Combustion Air

Installations in certain areas or types of structures will increase

the exposure to chemicals or halogens that may harm the fur­
nace.

The following areas or types of structures may contain or have ex­
posure to the substances listed below. The installation must be
evaluated carefully as it may be necessary to provide outside air
for combustion.

Commercial buildings.

Buildings with indoor pools.

Furnaces installed in laundry rooms.

Furnaces installed in hobby or craft rooms.

Furnaces installed near chemical storage areas.

Permanent wave solutions for hair.

Chlorinated waxes and cleaners.

Chlorine based swimming pool chemicals.

Water softening chemicals.

De-icing salts or chemicals.

Carbon tetrachloride.

Halogen type refrigerants.

Cleaning solvents (such as perchloroethylene).

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid.

Sulfuric Acid.

Solvent cements and glues.

Antistatic fabric softeners for clothes dryers.

Masonry acid washing materials.

Vent and Combustion Air Piping Guidelines

This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.

NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol­
vent cement, primers and procedures MUST conform to Ameri­
can National Standard Institute and American Society for Testing
and Materials (ANSI/ASTM) standards.

Pipeand Fittings - A S J M D M 8 5 ,

02241,02466, 02661,

02665, F-891, F-628

PVC Primer and Solvent Cement -

ASTM 02564

Procedure for Cementing Joints -

Ref ASTM 02855

NOTE: All vent piping MUST be installed in compliance with local
codes or ordinances, these instructions, good trade practices,
and codes of country havingjurisdiction.

1.

Determine the best routing and termination for the vent

pipe and air inlet pipe by referring to all of the instructions

and guidelines in this Section.

2. Determine the size required for the vent pipe and air inlet

pipe.

3.

Loosely assemble all venting parts without adhesive (pipe

joint cement) for correct fit before final assembly.

4.

Use of vertical piping is preferred because there will be

some moisture in the flue gases that may condense as it

leaves the vent pipe (See

Special Instruction For Horizon­

tal Vents).

5.

The vertical vent pipe MUST be supported so that no

weight is allowed to rest on the combustion blower.

6

. Exhaust vent piping or air inlet piping diameter MUST NOT

be reduced.

7.

All exhaust vent piping from the furnace to termination

MUST slope upwards. A minimum of V

4

" per foot of run is

required to properly return condensate to the furnace drain
system.

8

.

Use DWV type long radius elbows whenever possible, as

they provide for the minimum slope on horizontal runs and
they provide less resistance in the vent system. If DWV el­

bows cannot be used, use two, 45“ elbows when possible.
On horizontal runs the elbows can be slightly misaligned to
provide the correct slope.

9. All horizontal pipe runs MUST be supported at least every

five feet with galvanized strap or other rust resistant materi­
al. NO sags or dips are permitted.

10. All vertical pipe runs MUST be supported every six feet

where accessible.

11. The minimum pipe run length is 2'.

12. The piping can be run in the same chase or adjacent to sup­

ply or vent pipe for water supply or waste plumbing. It can
also be run in the same chase with a vent from another 90-r
furnace.

NOTE: In NO case can the piping be run in a chase where

temperatures can exceed 140“ F. or where radiated heat

_____ from adjacent surfaces would exceed 140° F.

44001

1114

00

Advertising
This manual is related to the following products: