Connecting vent pipes and termination, Horizontal termination, 1a#ari\iii\ib – Sears 9MPD User Manual

Page 27: Caution

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

NOTE:

Stirthesolventcementfrequently whileusing. Usea natu­

ral bristle brush or the dauber supplied with the cement. The prop­
er brush size is one inch.

2. After checking pipe and socket for proper fit, wipe socket

and pipe with cleaner-primer. Apply a liberal coat of primer

to inside surface of socket and outside of pipe. Do

NOT

al­

low primer to dry before applying cement.

3. Apply a thin coat of cement evenly in the socket. Quickly

apply a heavy coat of cement to the pipe end and insert
pipe into fittings with a slight twisting movement until it bot­

toms out.

NOTE:

Cement

MUST

be fluid while inserting pipe. If

NOT,

recoat

pipe.

4. Hold the pipe in the fitting for 30 seconds to prevent the ta­

pered socket from pushing the pipe out of the fitting.

5. Wipe all excess cement from the joint with a rag. Allow 15

minutes before handling. Cure time varies according to fit,

temperature and humidity.

Connecting Vent Pipes and Termination

NOTE:

Combustion air intake and vent

MUST

terminate in the

same atmospheric pressure zone. If installation is in a cold cli­
mate (sustained temperatures belowO°F), increase the minimum
distance between vent pipe and air intake from 8 " to 18".

CAUTION

Maintain a minimum of 36 ' between combustion air inlet and

clothes dryer vent. Terminate the combustion air intake as

far

as

possible

from

any

air

conditioner,

heat

pump,

swimming

pool,

swimming

pool

pumping,

chlorinator

or

filtration unit.

FIRE HAZARD

Observe all cautions and warnings printed on material
containers

to

prevent

possible

death,

personal

injury

and/or property damage.

Provide adequate ventilation and do NOT assemble near

heat source or open flame. Do NOT smoke while using

solvent cements and avoid contact with skin or eyes.

This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.

NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol­
vent cement, primers and procedures

MUST

conform to Ameri­

can National Standard Institute and American Society for Testing
and Materials (ANSI/ASTM) standards.

Pipe and Fittings -

ASTM D1785, D2241, D2466, D2661,

D2665, F-891,F-62S

PVC Primer and Solvent Cement -

ASTM D2564

Procedure for Cementing Joints ~

Ref ASTM D2S55

NOTE: In order to create a seal that allows future removal of pipe,

RTV sealant MUST be used on the inlet pipe

where it Joins to

the furnace. PVC, CPVC, ABS, and Cellular Core pipe and ce­
ment may be used on all otherjoints.

CAUTION

Do NOT use solvent cement that has become curdled, lumpy

or thickened and do NOT thin. Observe precautions printed

on containers. For applications below 32° F., use only low

temperature type solvent cement.

1.

Cut pipe end square, remove ragged edges and burrs.

Chamfer end of pipe, then clean fitting, socket and pipe

Joint of all dirt, grease, or moisture.

A

1A#ARI\III\IB

CARBON MONOXIDE POISONING HAZARD

Failure to properly vent this furnace can result in death,

personal injury and/or property damage.

1. Install all couplings, nipples and elbows using proper pro­

cedures for

Joining Pipe and Fittings

and maintain spac­

ing between vent and combustion air piping as indicated in

Figure 19

through

Figure 27 .

Horizontal Termination

1. Cut two holes.

2

V

2

" for 2" pipe, 3" for

2

V

2

" pipe, or

3

V

2

" for

3" pipe. Do NOT make the holes oversized, or it will be nec­
essary to add a sheet metal or plywood plate on the outside

with the correct size hole in it.

44001

1114

00

|~27М

Advertising
This manual is related to the following products: