Sizing, Insulation, Filters – Sears 9MPD User Manual

Page 35: Filter installation using optional filter rack, Connections

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

CARBON MONOXIDE POISONING HAZARD

This

could

result

in

death,

personal

injury

and/or

property damage.

Cool

air

passing

over

heat

exchanger

can

cause

condensate to form resulting in heat exchanger failure.

Connections

NOTE:

On upflow installations, return air can enter through either

side, both sides, or the bottom. On horizontal or downflow installa­
tions the return air must enter through the knockout opening in the
lower panel of the furnace. Return air

can not

enter through rear

of the furnace. When the furnace is located in an area near or ad­

jacent to the living area, the system should be carefully designed

with returns to minimize noise transmission through the return
grille. Any blower moving a high volume of air will produce audible

noise which could be objectionable to when the unit is located
very close to living areas. It is advisable to route the return air
ducts under the floor or through the attic.

1. For side connections using a 16" x 25" filter, cut out the em­

bossed area shown in

Figure 33.

This will provide a

I

4

V

2

"

X 2 2

V

2

" approximate opening.

NOTE:

Furnaces with 5 TONS cooling rating

require

two(2) side

returns or one side return with bottom return.

2.

Bottom returns can be made by removing the knockout

panel in the furnace base. Do

NOT

remove knock-out ex­

cept for a bottom return.

3. Installation of locking-type dampers are recommended in

all branches, or in individual ducts to balance system's air
flow.

4.

Non-combustible, flexible duct connectors are recom­

mended for return and supply connections to furnace.

5. If air return grille is located close to the fan inlet, install at

least one, 90° air turn between fan and inlet grille to reduce
noise.

NOTE

: To further reduce noise, install acoustical air turning vanes

and/or line the inside of duct with acoustical material.

Sizing

Existing or new ductwork MUST be sized to handle the correct

amount of airflow for either heating only or heating and air condi­
tioning.

Insulation

1

.

Insulate ductwork installed in attics or other areas exposed

to outside temperatures with a minimum of

2

" insulation

and vapor barrier.

2.

Insulate ductwork in indoor unconditioned areas with a

minimum of

1

" insulation with indoor type vapor barrier.

Filters

A Filter must be used:

Filters are not supplied with these furnaces, but can be purchased

from dealer.

Use either filter type:

• Washable, high velocity filters are based on a maximum

air flow rating of 600 FPM.

• Disposable, lowvelocityfiltersarebasedona maximum

air flow of 300 FPM when used with filter grille.

NOTE:

Disposable, low velocity filters may be replaced with

washable, high velocity filter providing they meet the minimum
size areas. Washable, high velocity filters can be replaced

ONLY

with same type and size.

Figuro 34 Side Mounted Filter Rack

Filter Installation using Optional Filter Rack

When installing or removing a bottom mounted filter, slidethe two
side filter clips to the back of the furnace

BEFORE

installing or re­

moving. This will allow the filter to clear the front raised edge of the
furnace. Insert filter into side clips first and push filter back until it is
fully engaged into back clip. When filter is in place, slide clips back
into place midway on filter as shown in

Figure 35.

Refer to

Figure

36 and for guidelines to install filters. Furnaces

which require larger filter media and have limited clearances on

44001

1114

00

rg)

Advertising
This manual is related to the following products: