Unconfined space installation – Sears 9MPD User Manual

Page 9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Figure 5

Outside Air (This is ONLY a guide. Subject to codes of country havingjurisdiction.)

(2) 1 Square Inch per 2000 BTÜH

4.

Size openings and ducts per

Table 1.

5.

Horizontal duct openings require 1 squareinchoffreearea
per 2,000 BTUH of combined input forall gas appliances in

area (see

Table 1).

6

. Vertical duct openings or openings directly to outside re­

quire 1 square inch of free area per 4,000 BTUH for com­

bined input of all gas appliances in area (see

Table

1).

Tabifi 1

Free Area

BTUH

Input

Rating

h/tinimum Free Area Required for Each Opening

Horizontal Duct

(2,000 BTUH)

Vertical Duct or openings

to outside (4,000 BTUH)

Round Duct

(4,000 BTUH)

50,000

25 sq.in.

12.5 sq. in.

4"

75,000

37.5 sq. in.

18.75 sq. in.

5"

100,000

50 sq.in.

25 sq. in.

6"'

125,000

62.5 sq. in.

31.25 sq. in.

7'

150,000

75 sq.In.

37.5 sq. in.

T

EXAMPLE:

Determining Free Area

Appliance 1 Appliance 2 Total Input

100.000 + 30,000 = (130,000 - 4,000) = 32.5 Sq. In. Vertical

Appliance 1 Appliance 2 Total Input

100.000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal

One permanent opening, commencing within 12" of the top of the
enclosure, shall be permitted where the equipment has clear­
ances of at least 1" from the sides and back and 6" from the front
of the appliance. The opening shall directly communicate with the
outdoors or shall communicate through a vertical or horizontal
duct to the outdoors or spaces (crawl or attic) that freely communi­
cate with the outdoors, and shall have a minimum free area of:

1 sq. in per 3000 Btu per hr. of the total input rating of all

equipment located in the enclosure, and

Not less than the sum of the areas of all vent connectors in

the confined space.

Unconfined Space Installation

CARBON MONOXIDE POISONING HAZARD

Failure to supply additional air by means of ventilation

grilles or ducts could result in death and/or personal

injury.

An unconfined space or homes with tight construction

may not have adequate air infiltration for proper

combustion and ventilation of flue gases.

Most homes will require additional air.

An unconfined space is defined as an area having a minimum vol­
ume of 50 cubic feet per 1,000 Btuh total input rating for all gas
appliances in area. Refer to

Table 2

for minimum area required.

Table 2 Unconfined Space

' ■ Minimum Area in Square Feet

BTUH Input

Rating

Minimum Area in Square Feet

50,000

312

78,000

490

114,000

712

155,000

968

EXAMPLE: NOTE: Square feet is based on 8 foot ceilings.

28.000 BTUH X 50 Cubic Et. = 1.400 = 175Sq. Et.

1,000 8' Ceiling Height

NOTE:

Refer to definitions in section titled

Unusually Tight

Construction.

If any oneof the conditions apply, the space

MUST

be considered confined space regardless of size.

1. Adjoining rooms can be considered part of an unconfined

area if there are openings without doors between rooms.

2. An attic or crawl space may be considered an unconfined

space provided there are adequate ventilation openings di­

rectly to outdoors. Openings

MUST

remain open and

NOT

have any means of being closed off. Ventilation openings to

outdoors

MUST

be at least 1" square of free area per 4,000

BTUH of total input rating for all gas appliances in area.

44001

1114

00

Advertising
This manual is related to the following products: