Using exterior risers, Vertical termination, Vent termination shielding – Sears 9MPD User Manual

Page 28: Multi vent termination clearances

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

2. Check hole sizes by making sure it is smaller than the cou­

plings or elbows that will be installed on the outside. The

couplings or elbows MUST prevent the pipe from being

pushed back through the wall.

3.

Extend vent pipe and combustion air pipe through the wall

^ / 4

" to T" and seal area between pipe and wall.

4.

Install the couplings, nipple and termination elbows as

shown and maintain spacing between vent and combus­
tion air piping as indicated in Figure 19 and Figure 20.

A metal shield is recommended 18 " x 18 " min. or 18 " min. diame­
ter around the vent termination at the exterior wall to protect the
house exterior materials from flue product or condensation (freez­
ing) damage.

Using Exterior Risers

1

.

Install elbows and pipe to form riser as shown in Figure 20.

2. Secure vent pipe to wall with galvanized strap or other rust

resistant material to restrain pipe from moving.

3. Insulate pipe with Armaflex or equivalent moisture resis­

tant closed cell foam insulation or Fiberglass insulation if

boxed in and sealed against moisture.

Vertical Termination

1

.

Figure 21 shows the proper installation and clearances for

vertical vent termination. The vertical roof termination
should be sealed with a plumbing roof boot or equivalent
flashing. The inlet ofthe intake pipeand end of the exhaust
vent must be terminated no less than

1

2"

above the roof or

snow accumulation level, and

1 2

" away from a vertical wall

or other protrusion.

2. If the vent system is installed in an existing chimney make

sure clearances shown in Figure 21 are maintained. Hori­
zontal section before the termination elbow can be ex­
tended on the inlet air to provide necessary clearance.

Vent Termination Shielding

Under certain wind conditions some building materials may be af­

fected by flue products expelled in close proximity to unprotected
surfaces. Sealing or shielding oftheexposed surfaces with a cor­
rosion resistant material (such as aluminum sheeting) may be re­
quired to prevent staining or deterioration. The protective material
should be attached and sealed (if necessary) to the building be­
fore attaching the vent terminal.

Multi Vent Termination Clearances

When two (2) or more furnaces are vented near each other, each
furnace must be individually vented.

Two (2) vent terminations may be installed as shown in

Figure 22, Figure 23, Figure 24, Figure 25, Figure 26 and
Figure 27, but the next vent termination must be at least 36" away

from first 2 terminations. It is important that vent terminations be
made as shown to avoid recirculation of flue gases.

[

2

^

44001

1114

00

Advertising
This manual is related to the following products: