Natural gas input rating check – Sears 9MPD User Manual

Page 32

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

FigurH 30

Typical Gas Piping for Downflow

Use elbows and 3" pipe nipple to connect valve

to piping when using left side gas pipe entry.

LP Low pressure

switch. Optional LP
conversion.

Drip Leg and Union, Union* should be outside

the cabinet. Manual shut-off valve MUST be

upstream of dripleg, union, and furnace.

Gas Pipe Grommet

‘Union may be installed inside the cabinet when necessary

(Single Pipe)

because of clearances.

25-23-39

Natural Gas Input Rating Check

NOTE: The gas meter can be used to measure input to furnace.
Rating is based on a natural gas BTU content of 1,000 BTU's per
cubic meter. Check with gas supplier for actual BTU content.

1. Makesureburnercompartmentdoorisinplace beforeper­

forming the following steps.

2. Turn OFF gas supply to all appliances and start furnace.

Example

Natural Gas

No. of Seconds

Time Per Cubic

BTU Per

BTU Content

Per Hour

Foot in Seconds

Hour

1,000

3,600

48

75,000

1,000

X

3,600 + 48 = 75,000 BTUH

3. Time how many seconds it takes the smallest dial on the

gas meter to make one complete revolution. Refer to

Ex­

ample.

Ì32l

44001

1114

00