Installation Requirements

1. Install furnace level.

2. This furnace is NOT to be used for temporary heat of build­

ings or structures under construction.

3. Install furnace as centralized as practical with respect to the

heat distribution system.

4. Install the vent pipes as short as practical. (See

Vent and

Combustion Air Piping

section).

5. Maintain clearance for fire safety and servicing. A front

clearance of 30" is required for access to the burner, con­
trols and filter.

6

.

Use a raised base for upflow furnace if the floor is damp or

wet at times.

7. For downflow installations, non combustible subbase must

be used under the furnace unless installation is on a non

combustible floor surface. This requirement applies even
when a coil box or cabinet is used.

A WARIMIIMG

FIRE HAZARD

Failure to install unit on noncombustible subbase can
result in death, personal injury and/or property damage.

Place furnace on noncombustible subbase on down­

flow

applications,

unless installing

on

non-combus­

tible flooring.

9. Residential garage installations require:

• Burners and ignition sources installed at least 18 " above

the floor.

• Located or physically protected from possible damage by

a vehicle.

10. Local codes may require a drain pan under the entire fur­

nace and condensate trap when the furnace is installed in
attic application.

Installation Positions

This furnace can be installed in an upflow, horizontal (either left or
right) or downflow airflow position. DO NOT install this furnace on
its back. For the upflow position, the return air ductwork can be
attached to either the left or right side panel and/or the bottom. For
horizontal and downflow positions, the return air ductwork must
be attached to the bottom. The return air ductwork must

never

be

attached to the back of the furnace.

Furnace Installation Considerations

The installation of the furnace for a given application will dictate
the position of the furnace, the airflow, ductwork connections,
vent and combustion air piping. Consideration must be given to
the following:

Condensate Trap and Drain Lines

The supplied condensate trap must be attached to the furnace
side panel on either the left or right side. For horizontal installa­
tions, the drain trap is vertically attached to the side panel below
the furnace. A minimum clearance of

6

" below the furnace is re­

quired for the condensate trap. Downward slope of the conden­
sate drain line from the condensate trap to the drain location must
be provided. Adequate freeze protection of the drain trap and the
drain line must be provided.

See" Condensate Drain

7rap"section

for further details.

Leveling

8

. For horizontal Installations, line contact is permissible only

between lines formed by Intersection of back and two sides

of furnace Jacket, and building joists, studs or framing.

Proper leveling of the furnace must be provided to insure proper

drainage of the condensate from the furnace. The furnace must
be level to within V

4

" from front to back and from side to side for

upflow and downflow Installations or top to bottom for horizontal
installations.

Vent and Combustion Air Connections

On the Dual Certified furnace, the vent and combustion air pipes
attach to the furnace through the top panel for the upflow and hori­
zontal installations. For the downflow installation, the vent and
combustion air pipes attach to the furnace through the alternate
locations on the furnace side panels.

Note: On the Direct Vent furnace, the vent pipe attaches to the fur­
nace through the side panels. The combustion air pipe attaches to

the top panel or to the alternate location on the side panel.

On the Single Pipe furnace, the vent pipe attaches to the furnace
through the furnace side panels.

Note: Repositioning of the combustion blower is required for the

vent pipe connection to the furnace through the "right side" panel.
See "

Vent and Combustion Air Piping"secûon

for further details.

CD

44001

1114

00