Horizontal telescopic flue, 1 flue length and restrictors – Glow-worm Betacom C User Manual

Page 21

Advertising
background image

21

14470

9 Telescopic Flue - Length, Preparation and Installation

9.1 Flue Length and Restrictors

The maximum permissable horizontal flue length is 2.5 metres

plus the flue terminal assembly, this can be achieved by use

of the accessories, see diagram 9.3.

However should an additional 90º or 2 x 45º elbows be used

then the length MUST be reduced by 1 metre.

The diagram 9.1 shows the length achievable by using the kit

A2043600.

When extension pipes are used the flue system must be

designed to have a continuous fall to the boiler of at least 2.5º

44mm/metre to allow condensate to run back into the boiler

and out via the condensate drain.

The flue can be installed from inside the building, when

access to the outside wall face is not practicable.

The flue restrictor is supplied in the documentation pack, the

correct size is supplied for the boiler output:-

Betacom 24c - 83mmØ

Betacom 30c - 85mmØ

The flue restrictor must be fitted in the flue adaptor for,

concentric flue installations less than 1 metre and twin flue

installations less than 2 metres equivalent length.

Full instructions are provided in the documentation pack.

Horizontal Telescopic Flue

Diagram 9.1