9 Plume Management Kit

9.25 Plume Management Kit

The Plume Management Kit: Part No. A2044100 (white) or

A2044000 (black) can be used to overcome many site issues.

The Plume Management Kit will fit to the Top Horizontal

Telescopic, Rear Horizontal Telescopic and Standard

Horizontal Flue. This enables the flue products to exhaust

further away from the boiler, thereby reducing the impact of

pluming.

NOTE: The flue air inlet can be sited closer to doors, opening

windows and air bricks, than stated in section 4.2, see

diagram 9.27.

The maximum length of the Plume Management Kit must NOT

exceed 2m with a horizontal concentric flue length of 1m max.

For each 90

o

bend or 2 x 45

o

bends the maximum length of the

Plume Management Kit must be reduced by 1m.

For more information contact Glow-worm, refer to page 2.

The Plume Management Kit is supplied with installation

instructions.

Refer to BS5546 or BS6798 for advice on disposal of boiler

condensate.

150mm.

MIN.

12997

Diagram 9.27

WARNING:

This appliance must be earthed.

● This appliance must be wired in accordance with these

instructions. Any fault arising from incorrect wiring cannot be

put right under the terms of the Glow-worm guarantee.

● All system components must be of an approved type.

Electrical components have been tested to meet the

equivalent requirements of the BEAB.

● Do not interrupt the mains supply with a time switch or

programmer.

● Connection of the whole electrical system and any heating

system controls to the electrical supply must be through a

common isolator.

● Isolation should preferably be by a double pole switched

fused spur box having a minimum contact separation of

3mm on each pole. The fused spur box should be readily

accessible and preferably adjacent to the boiler. It should be

identified as to its use.

● A fused three pin plug and shuttered socket outlet may be

used instead of a fused spur box provided that it is not used in

a room containing a fixed bath or shower.

● The boiler is suitable for installation in bathroom zones 2

and 3.

10 Electrical Connection

10.1 Electrical Wiring

The boiler is supplied factory wired complete with 1.5 m of

mains lead. All electrical connections to the mains supply must

be made in full accordance with the current I.E.E. regulations.

The boiler must be connected to an effective earth system.

A 3 amp fused three pin plug and shuttered socket outlet may

be used instead of a fused spur box provided that it is not

used in a room containing a fixed bath or shower.