8 rear flue, 9 side flue – Glow-worm Betacom C User Manual

Page 27

Advertising
background image

27

9.7 Standard Horizontal Flue - A2043400

Refer to diagram 9.11 for kit contents.

9.8 REAR Flue

T

emporarily

secure the

flue elbow, measure the distance

from the outside wall to the butt joint, see diagram

9.13

. If

the measurement ‘Y’ exceeds 665mm, then the appropriate

length of extension pipe is required. The minimum dimension

is 180mm to suit a 75mm min wall thickness. The flue can

project to a maximum of 600mm, refer to diagram 9.14.

9.9 SIDE Flue

T

emporarily

secure the

flue elbow, measure the distance

from the outside wall to the butt joint, see diagram

9.15.

If

the measurement ‘Y’ exceeds 665mm, then the appropriate

length of extension pipe is required. The minimum dimension

is 262.5 to suit a minimum wall thickness of 75mm. The flue

can project to a maximum of 600mm, refer to diagram 9.14.

9 Standard Flue - Length, Preparation and Installation