Glow-worm Betacom C User Manual

Page 45

Advertising
background image

45

To set the Minimum Setting:

Remove one lead from the gas valve modulating coil, see

diagram 11.17.

Turn boiler’s function switch to the ‘winter’ position (both CH

and DHW).

Turn the Central Heating temperature control knob to the

maximum position.

Connect a suitable pressure gauge to the pressure outlet

on the gas valve, see diagram 11.18.

Remove the protective cover from the gas valve.

Turn inner adjuster with a flat blade screwdriver.

Turn Clockwise: to increase burner pressure.

Turn Counter-Clockwise: to decrease burner pressure.

After adjustment, connect electrical lead and protective

cover.

To set the Maximum Setting:

Connect a suitable pressure gauge to the burner pressure

test point on the gas valve.

Remove the protective cover from the gas valve adjuster.

Connect a suitable pressure gauge to the pressure outlet of

the gas valve.

Turn boiler’s function switch to the ‘winter’ position.

Turn the Central Heating temperature control knob to the

maximum position.

Push the ball inside gas valve modulating coil using a sharp

pointed tool.

Turn outer nut with a 10mm spanner keeping the tool pushed

in:

Turn Clockwise: to increase burner pressure.

Turn Counter-Clockwise: to decrease burner pressure.

After adjustment, connect electrical lead and protective

cover.

11 Commissioning - Nat. Gas (G20) to LPG (G31) Conversion

Betacom 24c

Betacom 30c

NG

(G20)

mbar

LPG

(G31)

mbar

NG

(G20)

mbar

LPG

(G31)

mbar

Burner operating

pressure (minimum)

2.5

8.0

2.3

6.0

Burner operating

pressure (maximum)

12.5

36.5

14

36.0

Factory settings for DIP switches

DS1

DS2

DS3

DS4

DS5

DS6

DS7

DS8

Betacom 24c NG

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

Betacom 24c LPG

OFF

OFF

OFF

OFF

OFF

OFF

ON

OFF

Betacom 30c NG

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

Betacom 30c LPG

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

Diagram 11.18

15525

Diagram 11.17

15524

MODULATING

COIL

GAS VALVE

ADJUSTER

Dip switch 7 must be in the ON position for LPG and OFF for NG.

Dip switch 8 must be in the OFF position for Betacom 24c and ON for Betacom 30c.