9 Vertical Flue - Length, Preparation and Installation

9.11 Vertical flue

The vertical flue system is available as an option where the

boiler position does not permit the use of the top horizontal

flue system.

The system is made up from accessories. The accessories

include terminal assembly, bends 45º and 90º, flue

extensions, fixing bracket and appropriate weather collar,see

diagram 9.19.

The maximum permitted straight flue length is 6,8 metres for

Betacom 24C, 5,8 metres for Betacom 30C.

for each 90º or 2x45º bends fitted, the maximum length

must be reduced by 1 metre, see diagram 9.18.

NOTE: 2x45º bends can replace 1x90º bend if necessary.

When using 90º bends any horizontal extension pipe should

be inclined by a minimum of 44mm/metre (2.5º) towards the

boiler to facilitate condense removal, see (a) in diagram 9.18.

Alternatively use 45º bends to avoid horizontal runs, see (b)

in diagram 9.18.

The terminal siting should be as shown in diagram 4.2.

Measure the distance of flue length required for the

installation.

The flue must be designed with a continuous fall towards the

boiler.

The maximum permitted straight flue length

is 6,8 metres for Betacom 24C, 5,8 metres

for Betacom 30C, for each 90°or 45°x2

bends fitted, the maximum length must be

reduced by 1 metre.

w

w

E

1

E

1

E

2

E

2

Maximum flue (calculated equivalent) length
w, x, y, z, E

1

and E

2

should be less than 6.8 m for
Betacom 24c, 5.8 m for Betacom 30c