Installation – Glow-worm Clearly Hybrid - Back-up Module System User Manual

Page 11

Advertising
background image

0020096317_01 - 08/10 - Glow-worm

- 9 -

INSTALLATION

INSTALLATION

4 System appliance installation

4.1

Recommendations before installing

4.1.1

Heating circuit design

General

The heat transmitters may be low temperature (eg underfloor

heating or high temperature (radiator...).

The pipe sections are to be determined using a flow / pressure

curve (refer to the chapter "Activating the control unit" ►

Commissioning ► Heating circuit adjustment"). The distribution

will be determined by the flow corresponding to the power

actually required, regardless of the maximum power that can be

provided by the installation’s generators.

b

We recommend that you allow for sufficient flow

to ensure that the temperature difference between

the flow and the return is equal to 7 K for floor

heating and 15 K for radiators.

b

Make sure the heating circuit water flow is greater

than 900 l / h.

Installation pipework must be designed and installed to ensure

venting of air from the system is possible.

b

TRVs must be fitted on all radiators, with the

exception to reference rooms.

The total volume of water for the heating circuit depends,

among other factors, on the cold static load of the boiler’s

expansion vessel and the hydraulic module's expansion vessel.

i

The heating system volume should be calculated to

ensure that the expansion vessel is suitable, it may

be necessary to add an additional vessel.

- In GB, Guidance on vessel sizing is also given in the current

issue of BS5449 and BS7074 Part 1.

i

In the event of insolating the boiler, the boiler

expansion vessel will also be isolated from the

heating circuit.

In such an event, adopt the necessary precautions.

It is recommended that a drainage valve be installed at the

lowest point of the installation.

- Drain taps shall be to the current issue of BS2879.

• Install the following components in the return of the heating

circuit (not supplied):

- a heating filter

- a non-return valve (recommended)

- a ¼ turn shut-off valve,

- an air separator (if necessary),

- an anti-sludge filter (if necessary).

• In the case of a heated floor, install a manual reset overheat

safety device (55°C) on the heating circuit flow (refer to the

Chapter - System description). Connect the overheating

safety device to the boiler power supply.

Water treatment

existing system- It is essential that prior to installing the new

appliances the system is thoroughly flushed.

New system- For optimum performance after installation, the

appliances and its associated central heating system should

also be flushed.

Flushing shall be carried out in accordance with BS 7593, a

chemical cleanser can be used either Sentinel X300, X400 or

Fernox F3 are suitable.

It is recommended to flush existing systems first before fitting

the new appliances.

• Ensure all cleanser is removed from the whole system before

adding an inhibitor.

For long-term corrosion protection after flushing, an inhibitor

suitable for stainless steel heat exchangers can be used. Either

Sentinel X100 or Fernox F1 inhibitor can be used.

The module is suitable for use on systems using softened water.

4.1.2

Heat pump circuit design

Installation pipework must be designed and installed to ensure

venting of air from the system is possible.

b

Make sure the circuit’s water flow corresponds

to the appliance’s nominal water flow.

• Install the following components to the hydraulic module, in

the direction of the heat pump (not supplied):

- a filter,

- a ¼ turn shut –off valve on each side of the filter,

• Install a ¼ turn shutoff valve in the flow of the heat pump.

i

In order to avoid the transmission of vibrations to

surrounding structures, use hoses for the hydraulic

connections at least 1 metre from the heat pump.

b

Insulate the pipes with an UV- and high-

temperature-resistant insulation.

4.1.3

Domestic hot water circuit design

Water pressure

The maximum working pressure of the domestic hot water

circuit is 10 bar. If the cold water supply pressure exceeds this,

then a pressure-reducing valve must be fitted in the supply to

the boiler.

‘Hard’ water areas

In areas where the water is ‘hard’ (i.e. more than 200 mg/L

of calcium carbonate), it is recommended that the hot water

setting is reduced and that a scale reducer is fitted, refer to the

manufacturer’s instructions or consult the local water company

for additional advice.