INSTALLATION

Commissioning

• Open all the hydraulic circuits’ valves.

7 filling the glycol circuit

b

Warning! Do not dispose of glycol into drains

and the environment.

b

We recommend that you use propylene glycol

enriched with corrosive inhibitors.

• Mix 1 part propylene glycol with 2 parts water. This

mixture ensures antifreeze protection down to an exterior

temperature of -15 °C.

• Use an antifreeze test kit to ensure accurate dosing.

Ø14

A

B

1

3

4

1

2

Key

1 Air trap

2 Ø 14 mm flat wrench (*)

3 Hose

4 Deposit (*)

(*) Not included

• Connect one end of the hose (3) to the trap (1).

• Insert the other end of the hose (3) into the container (4) in

order to recover any residual brine during the filling of the

circuit.

• Using a flat wrench (2), open the trap (1) a ¼ turn.

1

2

3

4

A

B

5

6

8

7

Key

1 Glycol container (*)

2 Filling pump (*)

3 Hose leading to the filling pump output (*).

4 Cap

5 3-way valve with shut-off valve for filling

6 manometer

7 3-way valve with shut-off valve for filling

8 Hose leading to the filling pump return (*)

(*) Not supplied with the appliance

A Valve in filling mode

b Valve in normal operating mode

• In order to drain the glycol circuit after filling, use a fill pump

(2).

• Remove the caps (4) from the valves (5) and (7).

• Connect the filling pump hose (3) to the valve (5).

• Insert the hose (8) into the container and (1) and connect it

to the valve (7).

• Open valves (5) and (7) in (A) position as shown in the

illustration above.

• Start the fill pump (2) and fill the glycol circuit.

• Continue running the filling pump until completely purged of

air (8).

• Close the air trap located on the heat pump.

• Close the valve (7) in (B) position and ensure the glycol

circuit is left with a pressure of between 1.5 and 2 bars with

the aid of the manometer (6).

• Close the valve (5) in (B) position and stop the filling pump.