Maintenance, 3 status – Glow-worm Clearly Hybrid - Back-up Module System User Manual

Page 36

Advertising
background image

0020096317_01 - 08/10 - Glow-worm

- 34 -

MAINTENANCE

fault

codes Description

Cause

Solution

030

Failure in communication with the zone 1 wireless

room thermostat.

The room thermostat is too far from the

control unit.

There is a problem with the batteries in

room thermostat.

Check the RF signal quality via the

Climapro2 RF installer menu.

Check the location of the thermostat.

Check that the thermostat’s batteries are

installed in their compartment.

Make sure the battery polarity is not

reversed.

Make sure the batteries are not dead.

If so, replace them with new batteries

031

Failure in communication with the zone 2 wireless

room thermostat.

032

Failure in communication with the zone 3 wireless

room thermostat.

033

Failure in communication with the zone 4 wireless

room thermostat.

034

Failure in communication with the zone 5 wireless

room thermostat.

035

Failure in communication with the zone 6 wireless

room thermostat.

036

Failure in communication with the wireless

outdoor sensor

The wireless outdoor sensor is too far

from the control unit.

Check the location of the outdoor sensor.

Check that the sensor’s power supply is

correctly provided by a photovoltaic cell.

15.2.2

boiler fault codes

• Consult the boiler installation manual for information about

the fault codes.

15.2.3

Heat pump fault codes

• Consult the heat pump installation manual for information

about the fault codes.

15.3 Status

15.3.1

boiler status

• Consult the boiler installation manual for information about

the status codes.

15.3.2

Heat pump status

• Consult the heat pump installation manual for information

about the status codes.