MAINTENANCE

mAINTeNANCe

15 Trouble-shooting

15.1 fault diagnosis

The following checks should be performed before proceeding

onto specific diagnostics:

- Make sure that the electricity supply has not been interrupted

and that the appliance is connected correctly.

- Ensure that the isolating valves are open.

- Check that all external controls are connected correctly.

15.2 fault codes

i

The faults described in this chapter should be

carried out by a qualified engineer and if needed by

the After Sales Service.

15.2.1

System fault codes

fault

codes Description

Cause

Solution

001

Failure in Ebus communication between with the

boiler

The boiler is not connected to the control

unit.

The cable polarity is reversed.

The boiler is off.

Check that the boiler is connected to the

control unit.

Check the connection’s + / - polarity.

Ensure that there is no interruption to the

electricity network and that the boiler is

properly connected and turned on.

002

Failure in Ebus communication between with the

heat pump

The heat pump is not connected to the

control unit.

The heat pump is off.

Make sure the heat pump is connected to

the control unit.

Ensure that there is no interruption to the

electricity network and that the heat pump

is properly connected and turned on.

003

Failure in Ebus communication between with the

hydraulic module

The hydraulic module is not connected to

the control unit.

The hydraulic module is off.

Make sure that the hydraulic module is

connected to the control unit.

Ensure that there is no interruption to the

electricity network and that the hydraulic

module is properly connected and turned

on.

010

Heating circuit flow temperature sensor failure

(open circuit)

The sensor is defective or not

properly connected to the control unit

management or hydraulic module.

Check the sensor’s connections.

Verify that the position and the operation

of the sensor are correct.

Check the sensor’s resistance.

011

Heating circuit flow temperature sensor failure

(short circuit)

The sensor is shorted.

012

Heating circuit flow temperature sensor failure low

temperature (open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation

of the sensor are correct.

Check the sensor’s resistance.

013

Heating circuit flow temperature sensor failure low

temperature (short circuit)

The sensor is shorted.

014

Domestic water tank temperature sensor failure

(open circuit)

The sensor is defective or not properly

connected to the control unit.

Check the sensor’s connections.

Verify that the position and the operation

of the sensor are correct.

Check the sensor’s resistance.

015

Domestic water tank temperature sensor failure

(short circuit)

The sensor is shorted.

021

Pressure too low <0.5 bar

There is a leak in the heating circuit.The

venting was not carried out correctly.

Check that there are no leaks.

Drain the heating circuit. Remove air.

Fill the installation.