Minimum default maximum, Setpoint screen #5, Setpoint screen #6 – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 130: Setpoint screen #7

Advertising
background image

Section 3

Auto-Zone Plus

3-44

Programming

Setpoint Screen #5






Setpoint Screen #6





Setpoint Screen #7







CVAHU Setpoints

Minimum On/Off Times

Cool Staging: 4 Min

Cooling Off : 5 Min

The cooling stages must have been off for a minimum amount
of time before they can be activated or re-activated. As each
additional stage of cooling is added, a minimum Staging Delay
period
must be satisfied, between each additional stage
required.

Minimum Default Maximum

Cool Staging

1 Min

4 Min

30 Min

Cooling Off

1 Min

5 Min

30 Min

CVAHU Setpoints

Minimum On/Off Times

Heat Staging: 2 Min

Heating Off : 5 Min

The heating stages must have been off for a minimum amount
of time before they can be activated or re-activated. As each
additional stage of heating is added, a minimum Staging Delay
period
must be satisfied, between each additional stage
required.

Minimum

Default Maximum

Heat Staging

1 Min

2 Min

30 Min

Heating Off

1 Min

5 Min

30 Min

CVAHU Setpoints

Changeover Delay

Between Heat/Cool

Modes......: 15 Min.

To prevent rapid cycling back and forth between the heating
and cooling modes, the CVAHU has a programmable
Changeover Delay Timer. This timer prevents a change in
mode from bringing on any heating or cooling (based on last
mode) until this delay is satisfied.

Normally, you do not want to change modes more than four or
five times per hour.

Minimum Default Maximum

Changeover Delay

1 Min

20 Min

30 Min