Section 4

Auto-Zone Plus

4-30

Start-Up and Troubleshooting

2.2.9

Setting the Zone Manager Address Switches

SET THE ADDRESS

SWITCH LIKE THIS

( ADDRESS = 17 )

ALL ZONE MANAGERS MUST

BE SET TO ADDRESS 17

SET EACH ZONE MANAGERS

CLUSTER ADDRESS IN SEQUENCE

( ADDRESS = 1 SHOWN FOR FIRST UNIT )

EACH ZONE MANAGER MUST HAVE

A UNIQUE CLUSTER ADDRESS

1,2,3,4 ETC.

ZMGRSWP3.CDR 3/6/00

Remember - You must power down the Zone
Manager after changing the address switches
in order for any changes to take effect.

CLUSTER ADDRESS SWITCH

NETWORK SWITCH

IS ALWAYS "ON"

RIBBON CABLE MUST BE CONNECTED

NOT USED

NETWORK SWITCH MUST
BE IN OFF POSITION
IN ORDER FOR
MINILINK TO
FUNCTION

Figure 4-9:

Zone Manager Address Switches

CAUTION!

THE AUTO-ZONE Plus SYSTEM WILL NOT WORK PROPERLY
UNLESS YOU SET THE ADDRRESS SWITCHES CORRECTLY.