10 checking zone controller and cv unit drivers, Diagram meter set to read dc volts, Overview – Auto-Zone Control Systems Auto-Zone Plus Systems Installation & Operation (Version 03A) User Manual

Page 169: Measurements, Action

Advertising
background image

Auto-Zone Plus

Section 4

Start-Up and Troubleshooting

4-19

1.3.10

Checking Zone Controller and CV Unit Drivers

Diagram

Meter Set To Read DC Volts

T to SHLD

CV, CV-C

or Zone Controller

CV, CV-C

or Zone Controller

R to SHLD

+

-

T

R

SHLD

+

-

+2.4 VDC

to

+3.3 VDC

COMM

LOOP

T

SHLD

R

+

-

T

R

SHLD

+

-

+2.4 VDC

to

+3.3 VDC

COMM

LOOP

T

SHLD

R

Note: These tests assume that the controller being checked is powered up.

Overview

This check is intended to determine if the Comm Driver chip on a controller is damaged.
Damage typically occurs when the communications loop is exposed to excessive voltage, as
may occur during installation, due to wiring errors. The driver chips are socketed on all
boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.

Measurements

Local Loop

Acceptable Range

T – SHLD

2.4-to-3.3 Volts DC (Measured T-G and R-G Voltages should be within
0.1 VDC of each other)

R – SHLD

2.4-to-3.3 Volts DC (Measured T-G and R-G Voltages should be within
0.1 VDC of each other)

Note Minor variances may not indicate a problem if both tests indicate similar values.

Action

Condition Action

If voltages are outside the acceptable range
or T-G and R-G readings differ from each
other by more than 0.1 VDC

The controller has a damaged Comm
Driver chip. Replace the driver chip. See
"1.3.11Comm Driver Chip Replacement”.