Section 4

Auto-Zone Plus

4-48

Start-Up and Troubleshooting

4.2.4

Relay Output Descriptions

Output #1 - Main Fan ON/OFF Control

Output #2 - Mechanical Heating/Cooling Stage #1

Output #3 - Mechanical Heating / Cooling Stage #2

Output #4 - Mechanical Heating / Cooling Stage #3

Output #5 - Mechanical Heating / Cooling Stage #4

Any combination of heating and cooling stages may be configured during setup as long as
the required number of outputs does not exceed four. If heat is used, Output #2 will be the
first stage of heat, cooling stages will be after the heat.

4.2.5

RS-485 Communications Connector

This connector provides the connection point for the Local Loop RS-485 communications
loop. The wiring consists of a twisted pair of wires with a shield.

T - RS-485 (+) Communications terminal

SHLD
- Common return wire, this point is tied to GND on the CV Controller.

R - RS-485 (-)