3.5.2

Software

When using a pc to communicate with IQ

+

FLOW® instruments only the FLOW-BUS protocol is supported by Bronkhorst software.

When using Modbus operation, software from third parties, such as LabView, ModScan or a Modbus PLC must be used to serve as

Modbus master.

Note: an IQ

+

FLOW® instrument set for RS485 FLOW-BUS or Modbus communication will not respond when

connecting to an RS232 configuration. When required press the micro-switch according to the procedure in section

3.3.1 at start-up to activate the 'Configuration Mode'. The baud rate and bus type are set to 38k4 and RS232 FLOW-

BUS (Propar). For multi-channel instruments the communication type can be set with the rotary switches.

3.5.3

Slave address, baud rate and parity setup

The IQ

+

FLOW® instrument is configured as specified on order. If there is a need of changing any of the specified settings, see the

tables below for the supported configurations. The default selections are presented in bold.

Single-channel versions

Mode:

Analog

Digital

Interface/medium:

-

RS232

RS485

Bus protocol:

-

Propar

FLOW-BUS

Modbus RTU

Modbus ASCII

Baud rate:

-

9600

19200

38400

57600

115200

187500

400000

9600

19200

38400

56000

57600

115200

9600

19200

38400

56000

57600

115200

Node address:

-

3…125

3…125

1…247

1…247

Parity:

-

None*

None*

None; Even; Odd

None; Even; Odd

In case the baud rate or node address of an IQ

+

FLOW® instrument needs to be changed, this can be done with the micro-switch or

by changing the settings in the 'Configuration Mode'. Other parameters can be changed only in the 'Configuration Mode'. For

changing the mentioned parameters with the micro-switch see Section 4.2.5. When using the 'Configuration Mode' to change

these settings, activate the 'Configuration Mode' by pressing the micro-switch at start-up according the description in Section 3.3.1.

In 'Configuration Mode' the baud rate and bus type are set to 38k4 and RS232 FLOW-BUS (Propar). Change the appropriate

parameters as described in Section 4.2.5. When finished, deactivate the 'Configuration Mode' using the same procedure. Now the

instrument is ready to use in desired configuration with the adjusted baud rate, node address or parity.

Multi-channel versions (select with rotary switches)

Mode:

Digital

Interface/medium:

RS232

RS485

Bus protocol:

Propar

Modbus RTU

Baud rate:

38400

115200

9600

19200

38400

Node address:

3…99

1...99

Parity:

None*

Even

* Not selectable