5 changing slave address, baud rate and parity, Changing slave address, baud rate and parity – Bronkhorst IQ+FLOW (from 01-07-2013) User Manual

Page 27

Advertising
background image

Bronkhorst High-Tech B.V.

IQ+FLOW

27

9.17.045

4.2.4

Setting digital output (multi-channel versions only)

The IQ

+

FLOW® multi-channel pc-board is equipped with three digital outputs. The digital outputs can be used for driving shut-off

valves (for instance). The digital outputs can be read or written via the parameter 'IO Switch Status'. The parameters can be set as

indicated in the value table below. Note that this parameter is channel-independent. Each output can be accessed via all channels.

E.g. by writing this parameter via channel 2, it is possible to open/close a shut-off valve located at channel 1.

IO Switch Status

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned long

RW

0…7

288

114/31

0xF2F8/62201

Value

Status output 1

Status output 2

Status output 3

0

Off

Off

Off

1

On

Off

Off

2

Off

On

Off

3

On

On

Off

4

Off

Off

On

5

On

Off

On

6

Off

On

On

7

On

On

On

4.2.5

Changing slave address, baud rate and parity

Changing node address or baud rate by micro-switch operation

Press the micro-switch 5x briefly with intervals of max. 1 second in normal running/operation mode. Within the timeout period of

60 seconds it is possible to start changing the node address and baud rate of the instrument.

Step

Action

Indication

Time

Handling

1

Start

Press the switch 5x briefly with intervals of max. 1

second in normal running/operation mode.

2

Set tens of bus address

Green LED flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count green flashes for tens of

bus address.

Release when wanted amount has been count.

Counts up to max. 12 and than starts at 0 again.

When counting fails, keep switch pressed and

restart counting for next attempt.

3

Set units of bus address

red LED flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count red flashes for units of bus

address.

Release when wanted amount has been count.

Counts up to max. 9 and than starts at 0 again.

When counting failed, keep switch pressed and

restart counting for next attempt.

4

Set baud rate of field

bus communication.

1 = 9600 Baud

2 = 19200 Baud

3 = 38400 Baud

4 = 56000 Baud

5 = 57600 Baud

6 = 115200 Baud

both red and

green LEDs flashes

0.1 sec on, 0.1 sec off

count flashes

start when switch

is pressed:

0.5 sec on, 0.5 sec off

timeout:

60 sec

Press switch and count red and green flashes for

baud rate setting.

Release when wanted amount has been count.

Counts up to max. 5 and than starts at 0 again.

When counting failed, keep switch pressed and

restart counting for next attempt.

Note: selection of 0 means: No change

Instrument returns to normal running / operation mode. Changes are valid when they are made within the time-out times.

Advertising