Venting installation – Desa (V)CB36N(E) User Manual

Page 10

Advertising
background image

www.desatech.com

117437-01B

10

Lowest

Discharge

Opening

Listed

Vent Cap

8 Ft. Min.

Roof Pitch x/12

Listed Clearance

12

x

Listed

Gas

Vent

H (Min)

Height

From Roof

Figure 11 - B-Vent Termination

Roof Pitch

H (Min.)

Flat to /1

1.0 ft (0.3 m)

/1 to 7/1

1.5 ft (0.38 m)

Over 7/1 to 8/1

1.5 ft (0.4 m)

Over 8/1 to 9/1

.0 ft (0.1 m)

Over 9/1 to 10/1

.5 ft (0.7 m)

Over 10/1 to 11/1 3.5 ft (0.99 m)
Over 11/1 to 1/1 4.0 ft (1. m)
Over 1/1 to 14/1 5.0 ft (1.5 m)
Over 14/1 to 1/1 .0 ft (1.83 m)
Over 1/1 to 18/1 7.0 ft (.13 m)
Over 18/1 to 0/1 7.5 ft (.7 m)
Over 0/1 to 1/1 8.0 ft (.44 m)

VENTING INSTALLATION

Continued

CHECKING FOR PROPER VENTING

After completing and checking the electrical, gas

and vent connections, follow the lighting instruc-

tions and allow the main burner to run for approxi-

mately 5 minutes. Hold a match or butane lighter

flame, near the opening between the glass and the

fireplace face and play it along the entire length

of the opening (Smoke may also be used). Proper

venting will tend to draw flame or smoke into the

appliance. Improper venting, escaping or spillage

of burned gas, is indicated when the match flickers

or goes out (see Figure 12). Smoke will also tend

to disperse away from the appliance.

Figure 12 - Checking for Spillage

Figure 13 - Relocating Junction Box Recep-

tacle and Electrical Supply Connection

If the appliance is not venting properly, shut it

off and notify your installer or a qualified service

agency to inspect the venting system.

ELECTRICAL SUPPLY CONNECTION

CAUTION: Disconnect the

electrical power to the supply

circuit before attempting to con-

nect or service this appliance.

A prewired junction box receptacle with strain

relief is provided on the right side of the cabinet for

hard wiring the unit to a 15 Amp, 120 VAC, 60 Hz

grounded branch circuit. If the installation demands

that the electrical supply be connected from the left

side, the entire receptacle box can be relocated to the

left side by following these instructions:
Note:

If you do not need to relocate the junction

box, to connect the electric supply follow steps 8

through 11 only:

1. Remove 2 screws and outer cover with strain

relief bushing on right side of cabinet (see

Figure 13).

2. Remove inner retaining screw on junction box

mounting tab.

3. Slide junction box up until screw mounting

tab is lined up to notch in outer cabinet.

4. Swing junction box out and slip retaining

flange out through slot in outer cabinet.

5. Remove 2 screws and outer cover on left side

of outer cabinet.

6. Reinsert junction box retaining flange through

slot now on left side and swing screw mount-

ing tab back through notch as before.

7. Slide junction box down till mounting tab holes

line up and replace inner retaining screw.

8. With junction box cover removed, pull end

of 3-wire Romex supply line through uni-

versal strain relief bushing on cover. (see

Figure 13).

J-Box
Cover
with Strain
Relilef

J-Box
Cover

Romex
Cable

J-Box with
Receptacle

J-Box Cover
with Strain
Relief

Screw/Tab
Retainer