1.2 Target Evap Exit Temp INPUT FORM

Inputs

Into Evap Return DB

(Into Evaporator Return Dry Bulb)

Air tempera-

ture going into the evaporator. Take measurements as close to the air

handler as possible. If the filter is directly before the air handler clip the

included dry bulb thermocouple (ATA1) onto the filter. If the filter is

not just before the air handler drill small holes in the return plenum and

take measurements. Seal any holes before leaving the job site. Suggested

Accessories: ATH4, ATA1.

Into Evap Return WB

(Into Evaporator Return Wet Bulb) Use the wet

bulb thermocouple (ATWB1) and take measurement at the same place

as the Into Evap Return DB. Suggested Accessories: ATH4, ATWB1.

Out of Evap Supply DB

(Out of Evaporator Supply Dry Bulb) Air tem-

perature coming out of the evaporator. Punch or drill a small hole in

the supply plenum and measure in the center of the plenum. Suggested

Accessories: ATH4, ATB1.

Return Plenum Press

(Return Plenum Pressure) Optional. Static pres-

sure in the return plenum before the evaporator. Suggested Accessories:

ADMN2, ASP2.

Supply Plenum Press

(Supply Plenum Pressure) Optional. Static pres-

sure in the supply plenum after the evaporator. Suggested Accessories:

ADMN2, ASP2.

Customer ID

Used in the file name to save, recall and download tests. Use

arrow buttons to "type" in each character.

Units

Select English or Metric units.

Press enter to see a list of

saved Customer IDs or use

arrows to enter a new ID.

Target Evaporator Exit Temperature Test INPUT FORM filled.

Target Evaporator Exit Temperature Test INPUT FORM

continued from above.

Connect Accessory Head.

Scroll to highlight desired

parameter. Press enter to

start taking measurement.

Press enter again to lock

it in.

Take measurements using

Fieldpiece Accessory Heads

to automatically input

onto the INPUT FORM.

Measurements can also be

taken wirelessly. See page

12 for wireless instructions.

You can also enter

measurements manually

with the arrow buttons.

The negative sign is found

between 9 and 0.

Advertising