3.3 Subcooling OUTPUT FORM
Outputs

Target SC

(Target Subcooling) Indicates what the subcooling should be

from the manufacturer’s specifications. The HVAC Guide uses a built in

conservative estimate when manufacturer’s specifications are not avail-

able.

Actual SC

(Actual Subcooling) Displays the subcooling calculated from

the measured liquid line temperature and liquid line pressure.

Liquid Sat

This is the saturation temperature of the refrigerant in the con-

denser coil. It is one of the temperatures from which subcooling is cal-

culated.

Suggested Actions

Suggested actions are displayed to correct the

problem. Use the down arrow to scroll down the OUTPUT FORM.

Because everything within the system is interdependent, one adjust-

ment can affect the whole system. Tests should be used together such

as Subcooling to correct refrigerant charge and Target Evap Exit

Temp to correct airflow across the evaporator coil.

See Sec

(See Section) The section numbers on the OUTPUT FORM refer to

the sections in this manual with more detailed information about each

test.

Subcooling OUTPUT FORM.

Subcooling OUTPUT FORM continued from above.

Compare the Actual SC to the

Target SC. Actual subcooling

should be within about 3°F

the target subcooling.

The OUTPUT FORM displays

the results of the test.

Keep scrolling through the

OUTPUT FORM to see all

suggested actions.

Use suggested actions to fix

the problem. Scroll down

with the arrows to see more.