Superheat Overview

Superheat is the temperature rise above the boiling point of the refriger-

ant. Too high, and the refrigerant boils off early in the evaporator and wastes

most of the capacity of the evaporator. Too low, and you risk liquid going into

the compressor.

Using superheat is the best way to obtain proper refrigerant charge for a

fixed restrictor metering device system.

If the air conditioner is in good working order and the airflow is adjusted

properly, comparing the actual and target superheat will tell you if refriger-

ant needs to be added or recovered. Ensure the pressure never exceeds the

manufacturer's maximum overload pressure guidelines.

On a fixed restrictor system, the target superheat is determined based

upon the indoor wet bulb and outdoor dry bulb temperatures.

The Actual SH (superheat) should be within ±5°F of the Target SH to

ensure optimum performance. If the actual SH is outside this range, modi-

fications to the charge or adjustments to the restrictor (TXV) are necessary.

Adding refrigerant lowers Actual SH. Recovering refrigerant increases

your Actual SH. The amount of refrigerant necessary to add or recover will

vary based on the size of the system and the difference between the Actual

and Target SH.

To get Actual Superheat, you need to measure suction line pressure and

suction line temperature. To get Target Superheat heat for fixed restrictor sys-

tems you need to measure return air wet bulb and outdoor dry bulb.

Because everything within the system is interdependent, one adjustment

can affect other parts of the system. For example, increasing airflow increases

the superheat, which may require adding refrigerant. After modifications, al-

low 15 minutes to stabilize and then retest.

Refrigeration Cycle

Use the HG3, ASX14 and ATC1

to get actual superheat.

EVAPORATOR

CONDENSER

THROTTLE

VALVE

COMPRESSOR

REFRIGERANT

FLOW

H

ig

h P

ress

ure Side

Low Press

ure

Sid

e

RETURN AIR

SUPPLY AIR

OUTDOOR AIR

HOT AIR

AA

V3

Air V

elocity

& T

emper

atur

e

Accessor

y

Head

ON

LCD

X100

LO BA

TT

READ

ENGLISH

ENGLISH

METRIC

Ft/min

MPH

°F

M/s

KM/hr

°C

METRIC

AV

G

NORMAL

ATH4

AUT

O OFF

ARH4

T1-T2

T2

T1

Function

T1

CAL

T2

CAL

AUT

O OFF

°C

°F

T1

T2

Set meter to mVDC

range to display

temperature directly

.

LO BA

TT

ON

Dual

Temper

atur

e

Head

OFF

ATH4

T1-T2

T2

T1

Function

T1

CAL

T2

CAL

AUT

O OFF

°C

Set meter to mVDC

range to display

temperature directly

.

LO

BA

TT

ON

Dual

Temper

atur

e

Head

OFF

ASX14

ACH4

Sync

ET2W

Air

Conditioner

Superhea

t and

Subcooling

AUT

O

OFF

T/C

CAL

ATH4

T1-T2

T2

T1

Function

T1

CAL

T2

CAL

AUT

O OFF

°C

°F

T1

T2

Set meter to mVDC

range to display

temperature directly

.

LO BA

TT

ON

Dual

Temper

atur

e

Head

OFF

SET

AT

M

ST

ABLE

ON

LO BA

TT

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sling

Psy

chr

ometer

Head

ON

AUT

O OFF

1%RH/mVDC
1°F/mVDC

1°C/mVDC

LO BA

TT

DEW POINT

%RH

WET B

ULB

TEMP

°F

°C

ON

OFF

ACM3

AOX

2

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Sync

ET2W

MAX 30VDC
24VAC

CONNECT ONLY TO

ACCESSORY HEAD!

LO BA

TT

SEND

RECEIVE

ON

AC

DC

W

ireless

Transmitter

Carbon

Mono

xide

Accessor

y

Head

ON

Converts

1PPM CO

concentration

to 1mVDC

LO BA

TT

ON

OF

F

AVERA

GE

NORM

AL

AUT

O

OFF

ZERO

SET

CA

T.III

300V

400A

CLAM

P

AC Cur

rent

Clamp

1AAC / 1mV

AC

400AAC MAX

!

Combustion

Chec

k

%O

%CO

TEMP

ON

GAS

OIL

Lo Batt

°C °F

AUT

O

OFF

ST

ABLE

Fuel T

ype

2

2

T/C

CAL

ARH4

Sling

Psy

chr

ometer

Head

ON

AUT

O OFF

1%RH/mVDC
1°F/mVDC

1°C/mVDC

LO BA

TT

DEW POINT

%RH

WET B

ULB

TEMP

°F

°C

ON

OFF

ATH4

T1-T2

T2

T1

Function

T1

CAL

T2

CAL

AUT

O OFF

°C

°F

T1

T2

Set meter to mVDC

range to display

temperature directly

.

LO BA

TT

ON

Dual

Temper

atur

e

Head

OFF

AA

V3

Air V

elocity

& T

emper

atur

e

Accessor

y

Head

ON

LCD

X100

LO BA

TT

READ

ENGLISH

ENGLISH

METRIC

Ft/min

MPH

°F

M/s

KM/hr

°C

METRIC

AV

G

NORMAL

AUT

O OFF

AOX

2

Combustion

Chec

k

%O

%CO

TEMP

ON

GAS

OIL

Lo Batt

°C °F

AUT

O

OFF

ST

ABLE

Fuel T

ype

2

2

T/C

CAL

ACM3

Carbon

Mono

xide

Accessor

y

Head

ON

Converts

1PPM CO

concentration

to 1mVDC

LO BA

TT

ON

OFF

AVERA

GE

NORM

AL

AUT

O

OFF

ZERO

SET

ACH4

CA

T.III

300V

400A

CLAM

P

AC Cur

rent

Clamp

1AAC / 1mV

AC

400AAC MAX

!

ASX14

Air

Conditioner

Superhea

t and

Subcooling

AUT

O

OFF

T/C

CAL

SET

AT

M

ST

ABLE

ON

LO BA

TT

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Jacket

Charging

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Light

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Service

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Light

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Service

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Clear

Input

Output

Sync

Recall

Enter

Save

MAX 30VDC

24VAC

CONNECT ONLY TO

ACCESSORY HEADS!

HVAC Guide

Fieldpiece

HG3

SETUP

Target

Evaporator

Logger

Exit Temp

CFM

Display

Superheat

Subcooling

Combustion

CheckMe!

Data

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

Jacket

Charging

OUTPUT FORM

CO2: 6.3%

Excess O2:

76.8%

COAF: 103ppm

Net Temp:

82 ˙F

Standard Eff:

85%

Siegert Eff:

94%

Draft Press: 0.08IWC

INPUT FORM

Pressure is between

160psig and 220psig.

SL Pressure: ---.-psig

LL Pressure: ---.-psig

Difference: ---.-psig

Confirm Pressures

CustomerID: __JONES123

INPUT FORM

SH Table:Standard

Refrigerant:R-22

OD Dry Bulb:

85.4˙F

Return WB:

61.0˙F

SL Pressure

:

---.-˙F

SL Temp:

--.-˙F

CustomerID:__JONES123

INPUT FORM

Into Evap

Return DB

: 72.1˙F

Return WB:

64.5˙F

Out of Evap

Supply DB:

55.6˙F

CustomerID: __JONES123

Units:English

INPUT FORM

Span: 2hours

Per: 30seconds

SEY

SET ID:IndoorTemp

Measurement: 72.8

SET ID:CompAmps

Measurement: 17.2

INPUT FORM

ACV

CustomerID

:--JONES123

01/24/2000 04:20:22PM

OUTPUT FORM

CO2: 6.3%

Excess O2:

76.8%

COAF: 103ppm

Net Temp:

82 ˙F

Standard Eff:

85%

Siegert Eff:

94%

Draft Press: 0.08IWC

INPUT FORM W/O

Manufacturer’s Data

Refrigerant: R-22

LL Pressure: 220.3psig

LL Temp

:

91.1˙F

CustomerID:__JONES123

Units:English

12/31/2011 11:59:59PM

INPUT FORM W/O

Manufacturer’s Data

Refrigerant: R-22

LL Pressure: 220.3psig

LL Temp

:

91.1˙F

CustomerID:__JONES123

Units:English

12/31/2011 11:59:59PM

INPUT FORM

Into Evap

Return DB:

72.1˙F

Return WB:

64.5˙F

Out of Evap

Supply DB

:

55.6˙F

CustomerID: __JONES123

Units:English

INPUT FORM

Refrigerant:R-410A

Constrict the

Charging Jacket until

the difference

between the SL

Pressure and LL

Pressure is between

INPUT FORM

SH Table:Standard

Refrigerant:R-22

OD Dry Bulb:

85.4˙F

Return WB:

61.0˙F

SL Pressure

:

---.-˙F

SL Temp:

--.-˙F

CustomerID:__JONES123

INPUT FORM

Sys Type

:AC

Grant and Sys Info:

None

INDOOR UNIT

Meter Device:TXV/TEV

Return DB:

71.7˙F

Return WB:

60.8˙F

INPUT FORM

Sys Type

:AC

Grant and Sys Info:

None

INDOOR UNIT

Meter Device:TXV/TEV

Return DB:

71.7˙F

Return WB:

60.8˙F

Memory:

Com with PC

Erase a Single Test

Erase a Customer

Erase a Grant

Check Memory Status

Clear Data logs

Clear All Data

Memory:

Com with PC

Erase a Single Test

Erase a Customer

Erase a Grant

Check Memory Status

Clear Data logs

Clear All Data

INPUT FORM

SET ID:IndoorTemp

Measurement: 72.8

SET ID:CompAmps

Measurement: 17.2

Span: 2hours

Per: 30seconds

START

INPUT FORM

DCV

CustomerID

:--JONES123

01/24/2000 04:20:22PM

INPUT FORM

Grille 01

ID:LivingRm1

Flow:Supply

Manufacturer’s Data

Free Area in sqft:

00.421sqft

Velocity

: 212ft/min

INPUT FORM

Grille 01

ID:LivingRm1

Flow:Supply

Manufacturer’s Data

Free Area in sqft:

00.421sqft

Velocity

: 212ft/min

INPUT FORM

Into Evap

Return DB:

72.1˙F

Return WB:

64.5˙F

Out of Evap

Supply DB:

55.6˙F

CustomerID

: __JONES123

Units:English

ARH4

Sling

Psychrometer

Head

ON

AUTO OFF

1%RH/mVDC

1°F/mVDC

1°C/mVDC

LO BATT

DEW POINT

%RH

WET BULB

TEMP

°F

°C

ON

OFF

ATH4

T1-T2

T2
T1

Function

T1

CAL

T2

CAL

AUTO OFF

°C

°F

T1

T2

Set meter to mVDC

range to display

temperature directly.

LO BATT

ON

Dual

Temperature

Head

OFF

ATH4

T1-T2

T2
T1

Function

T1

CAL

T2

CAL

AUTO OFF

°C

°F

T1

T2

Set meter to mVDC

range to display

temperature directly.

LO BATT

ON

Dual

Temperature

Head

OFF

AAV3

Air Velocity

& Temperature

Accessory

Head

ON

LCD

X100

LO BATT

READ

ENGLISH

ENGLISH METRIC
Ft/min

MPH

°F

M/s

KM/hr

°C

METRIC

AVG

NORMAL

AUTO OFF

AOX2

Combustion

Check

%

O

%

CO

TEMP

ON

GAS

OIL

Lo Batt

°C °F

AUTO

OFF

STABLE

Fuel Type

2
2

T/C

CAL

ACM3

Carbon

Monoxide

Accessory

Head

ON

Converts

1PPM CO

concentration

to 1mVDC

LO BATT

ON

OFF

AVERAGE

NORMAL

AUTO

OFF

ZERO

SET

ACH4

CAT.III

300V
400A

CLAMP

AC Current

Clamp

1AAC / 1mVAC

400AAC MAX

!

ASX14

Air

Conditioner

Superheat and

Subcooling

AUTO

OFF

T/C

CAL

SET

ATM

STABLE

ON

LO BATT

Advertising