4.2 Combustion INPUT FORM
Inputs

Fuel

Select Natural Gas, Oil #2 or Propane.

Type

Default: Condensing. Other selection: Non-Condensing. The pres-

ence of a condensate line indicates a condensing unit, otherwise it is a

non-condensing unit.

Primary Temp

(Primary Temperature) Measure the temperature of the

air being introduced to the combustion process.

O

2

(Oxygen) Connect the AOX2 with the switch on %O

2

and take a sample

of the combustion products in the flue/stack (within 18 inches from the

start of the flue).

Flue Temp

(Flue Temperature) Connect the ATR1 temperature probe to

the AOX2. Set the AOX2 on TEMP and measure the temperature of the

combustion products in the flue/stack (18 inches from the start of the

flue).

CO

(Carbon Monoxide) Connect a flue gas CO detector and take a sample

of the combustion products in the flue/stack in the same location as the

O2% measurement (within 18 inches from the start of the flue). Enter

your measured CO value into the HG3 for calculation.

Draft Press

(Draft Pressure) Air pressure taken in the flue. Suggested Ac-

cessories: ADMN2, ASP2.

Customer ID

Used in the file name to save, recall and download tests. Use

arrow buttons to "type" in each character. Press RIGHT arrow to get to

the first character. Once complete press ENTER to lock it in.

Units

Select English or Metric units.

Combustion Analysis INPUT FORM.

Fuel drop down menu.

Press Enter to see the fuel list.

Take measurements using

Fieldpiece Accessory Heads

or manual entry.

Scroll to appropriate Fuel

using the UP/DOWN Arrows.

Press Enter to lock it in.